Unitary Valve Actuator

M6410; M7410

Cartridge Globe Valve Actuator are small electric actuators for individual room control that provide floating or modulating control of V5852, V5862 two-way or V5853, V5863 three-way valves.

SPECIFICATIONS

 

Actuator Type

Valve

Control Signal

Floating; 0-10Vdc or

 

2-10Vdc modulating

Fail Safe Mode

Stays in place

Cable Entry

Threaded conduit connector

Electrical Protection

Class I Insulation (24 Vac)

Ingress Protection Rating

IP42

Electrical Connections

Plenum-rated cable

Feedback

No

Frequency

50 Hz, 60 Hz

Manual operation

Use valve dust cap

Mounting

Threads onto V58XX valve

 

bonnet

Stroke

1/4 in. (6 mm)

Supply Voltage

20 to 28 Vac

Number of Internal Auxiliary Switch

0

Materials

Low Maintenance Plastic

 

Housing

Operating Humidity Range (% RH)

5 to 95% RH

Medium Temperature

266 F Maximum (130 C

 

Maximum)

Ambient Temperature Range

32 F to 122 F (0 C to 50 C)

Storage Temperature Range

-40 F to 158 F (-40 C to 70 C)

Weight

0.3125 lb (0.15 kg)

Includes

1/2 in. conduit hub

APPROVALS

 

Underwriters Laboratories, Inc

UL94-5V

 

 

FEATURES

Suitable for Excel/IRC system or other controllers providing specified signals.

Magnetic coupling for torque limitation independent of voltage supply and self-adjustment of the close-off port.

No mounting tools required.

Small size allows installation in limited space of fan coil units, induction units, and small reheaters or recoolers.

Visual position indication (red pin).