Toshiba HWS-1402H-E Diagnosis flow chart for each error code, Hydro unit failure detection

Models: HWS-1402XWHT9-E HWS-1402XWHM3-E HWS-1402XWHT6-E HWS-1501CSHM3-E(-UK) HWS-1402H-E HWS-2101CSHM3-E(-UK) HWS-3001CSHM3-E(-UK) HWS-802XWHM3-E HWS-802H-E HWS-802XWHT6-E

1 168
Download 168 pages 43.83 Kb
Page 75
Image 75
9-4. Diagnosis flow chart for each error code

9-4. Diagnosis flow chart for each error code

9-4-1. Hydro unit failure detection

[A01] Error Pump flow determination

Perform air vent

Yes

[A01] occurs

Operation restarts

Pump rotates

No (No pump sound)

 

 

 

Yes

Flow switch is

No

 

connected to board

 

Excess air noise

Yes

 

comes from inside

 

 

the pump

 

 

Connect flow switch connector to board

No

Built-in pump is

No

 

connected to board

 

 

Yes

 

Connect pump connector to board

 

Flow switch is normal

No

Replace flow switch

 

 

Chattering noise comes

No

 

 

 

 

from flow switch

 

Yes

 

 

No

 

 

 

Replace pump

 

 

 

 

 

 

 

Pump stops 2-3

Yes

 

 

minutes after its rotation

 

 

 

 

started

 

 

 

 

No

Flow shortage

(Identify causes, and resolve)

TC sensor characteristic

No

 

is correct

 

Yes

 

 

 

 

Replace TC sensor

 

 

 

 

 

 

 

 

 

Dirt clogging inside

 

 

 

 

Remove waste

 

water circuit

 

 

 

 

 

 

 

 

 

(strainer)

 

 

 

 

 

 

12 M or longer water

 

Fit buffer tank and the

 

pipe to a branch,

 

 

 

second pump

 

or 5 or less branches

 

 

 

 

 

 

 

 

Flow switch is normal

Yes

No

Attach or replace

flow switch

Water heat exchanger control board is defective, replace it

74

Page 75
Image 75
Toshiba HWS-1402H-E, HWS-802XWHT6-E, HWS-802H-E Diagnosis flow chart for each error code, Hydro unit failure detection