Toshiba HWS-802H-E, HWS-802XWHT6-E, HWS-802XWHM3-E Defect mode detected by the outdoor unit

Models: HWS-1402XWHT9-E HWS-1402XWHM3-E HWS-1402XWHT6-E HWS-1501CSHM3-E(-UK) HWS-1402H-E HWS-2101CSHM3-E(-UK) HWS-3001CSHM3-E(-UK) HWS-802XWHM3-E HWS-802H-E HWS-802XWHT6-E

1 168
Download 168 pages 43.83 Kb
Page 71
Image 71

Defect mode detected by the outdoor unit

 

 

 

 

 

O ... Possible

 

 

 

 

 

× .... Not possible

 

 

 

 

 

 

 

 

Diagnostic functional operation

 

 

Number of

 

Check

 

 

 

Determination and action

abnormalities

Detailed

 

 

 

code

 

Backup

Automat

for

item

Operational cause

 

 

present

ic reset

 

confirmation

 

 

 

 

 

 

 

 

 

 

 

 

 

TD sensor error

 

 

1. Check the resistance value and

 

85

F04

Open or short circuit in the discharge

O

×

connection of the discharge sensor

1

99

 

temperature sensor.

 

 

(TD).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TE sensor error

 

 

1. Check the resistance value and

 

85

F06

Open or short circuit in the heat

O

×

connection of the heat exchange

1

99

 

exchange temperature sensor.

 

 

temperature sensor (TE).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TL sensor error

 

 

1. Check the resistance value and

 

86

F07

Open or short circuit in the heat

O

×

connection of the heat exchange

1

99

 

exchange temperature sensor.

 

 

temperature sensor (TL).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TO sensor error

 

 

1. Check the resistance value and

 

86

F08

Open or short circuit in the outdoor

O

×

connection of the outdoor

1

99

 

temperature sensor.

 

 

temperature sensor (TO).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TS sensor error

 

 

1. Check the resistance value and

 

 

F12

Open or short circuit in the suction

O

×

connection of the suction

1

100

 

temperature sensor.

 

 

temperature sensor (TS).

 

 

 

 

 

 

 

 

 

 

TH sensor error

 

 

1. Check the resistance value and

 

 

F13

Open or short circuit in the heat-sink

O

×

connection of the heat-sink

1

100

 

temperature sensor.

 

 

temperature sensor (TH).

 

 

 

 

 

 

 

 

 

 

TE, TS sensors error

 

 

1. Check for any wrong installation of

 

 

F15

Open or short circuit in the temperature

O

×

the heat exchange temperature

1

100

 

sensor (TE) and the suction

 

sensors.

 

 

 

 

 

 

 

temperature sensor (TS).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F31

EEPROM error

O

×

 

1

100

 

 

 

 

 

 

 

 

Compressor breakdown

 

 

 

 

 

 

1 When the operation frequency lowers

 

 

 

 

 

 

due to the current release 40 sec or

 

 

 

 

 

 

later after the compressor activation

 

 

1. Check the power supply voltage

 

 

 

and it stops by underrunning the

 

 

 

 

 

 

 

(AC230 V±23 V).

 

 

 

minimum frequency.

 

 

 

 

 

 

 

2. Over-loaded condition of the

 

 

H01

2 When the operation frequency lowers

O

×

8

91

refrigeration cycle.

 

due to the current limit control and it

 

 

 

 

 

 

 

3. Check that the service valve is fully

 

 

 

stops by underrunning the minimum

 

 

 

 

 

 

 

open.

 

 

 

frequency.

 

 

 

 

 

 

 

 

 

 

 

3 When an excess current is detected

 

 

 

 

 

 

0.8 sec or later after the compressor

 

 

 

 

 

 

activation.

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor lock

 

 

1. Defect of compressor (lock)

 

 

 

 

 

 

 

 

 

1 When the input current is more than

 

 

– Replace the compressor.

 

 

H02

 

O

×

8

92

zero 20 sec or later after the

2. Defect of compressor wiring (open

 

compressor activation and the

 

 

 

 

 

 

 

phase).

 

 

 

activation has not been completed.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H03

Defect in the current detection circuit

O

×

1. Replace the outdoor inverter control

8

92

 

 

 

 

board.

 

 

 

 

 

 

 

 

 

70

Page 71
Image 71
Toshiba HWS-802H-E, HWS-802XWHT6-E, HWS-802XWHM3-E, HWS-3001CSHM3-E(-UK) Defect mode detected by the outdoor unit