Toshiba HWS-3001CSHM3-E(-UK), HWS-802XWHT6-E, HWS-802H-E, HWS-1402H-E Usual, when TO sensor fails

Models: HWS-1402XWHT9-E HWS-1402XWHM3-E HWS-1402XWHT6-E HWS-1501CSHM3-E(-UK) HWS-1402H-E HWS-2101CSHM3-E(-UK) HWS-3001CSHM3-E(-UK) HWS-802XWHM3-E HWS-802H-E HWS-802XWHT6-E

1 168
Download 168 pages 43.83 Kb
Page 63
Image 63
(Usual)

Item

Operation flow and applicable data, etc.

 

 

8-4.

7) Winding heating control

Outdoor unit

1) This control energizes the inactive compressor instead of the case heater to warm the compressor. The purpose is

control

to prevent the refrigerant from staying inside the compressor.

2)After the unit is installed, failure to perform energization for the given time period may cause the compressor to fail. Also, when starting an operation long after the power left off, first energize the compressor before starting the operation in the same way as a trial run.

3)Energization is determined by the TD sensor and TO sensor. If the TO sensor fails, the TE sensor automatically takes over the operation. Determine whether the TO sensor fails by checking the LED outside.

4)If TD is 30°C or higher, the energization stops.

 

TO

(Usual)

 

Not energized

 

18°C

 

 

*Energization

15°C

Intermittently energized

condition

 

TD 30°C

10°C

10 mins: ON / 5 mins: OFF

 

8°C

Output "equal to 40W"

 

Continuously energized

 

 

 

 

Output "equal to 40W"

 

 

 

 

TE

(when TO sensor fails)

 

Not energized

 

20°C

 

 

*Energization

18°C

Intermittently energized

condition

 

TD 30°C

12°C

10 mins: ON / 5 mins: OFF

 

10°C

Output "equals to 40W"

 

Continuously energized

 

 

 

 

Output "equals to 40W"

 

 

 

Notes

During winding energization, energizing noise may be heard, but this is not abnormal.

8)Short circuit operation prevention control

1)In 10 minutes after the operation start, the compressor may not stop for protection. This status is not abnormal. (The operation duration time of the compressor varies depending on a operation status.)

2)If the operation stops with the remote controller, the operation does not continue.

9)Over current protection control

1)A detection of abnormal current with the over current protection control stops the compressor.

2)Set the abnormality detection counter to 1, and restarts the compressor after 150 seconds.

3)When the stop by over current protection control counts 8 times, error code is displayed and the compressor does not restart.

(Remote controller error code display: HO1)