Toshiba HWS-1402XWHT9-E, HWS-802XWHT6-E, HWS-802H-E A05 Error Piping freeze prevention control

Models: HWS-1402XWHT9-E HWS-1402XWHM3-E HWS-1402XWHT6-E HWS-1501CSHM3-E(-UK) HWS-1402H-E HWS-2101CSHM3-E(-UK) HWS-3001CSHM3-E(-UK) HWS-802XWHM3-E HWS-802H-E HWS-802XWHT6-E

1 168
Download 168 pages 43.83 Kb
Page 79
Image 79
[A05] Error Piping freeze prevention control

[A05] Error Piping freeze prevention control

Restart

TWIManual background4, TWOManual background 4, or

THOManual background4 is detected

Circulation pump keeps

being energized or 3 minutes passed after the start

Water heat

No

 

exchange control board

 

 

 

DPSW11-1 is ON

 

 

Yes

 

 

Backup heater terminal

No

 

has 230ACV ( ± 23V)

 

 

Yes

Power is connect to

No

 

built-in heater terminal

 

 

Yes

 

Backup heater element

No

 

is conductive

(Backup heater NG)

Yes

 

TWI, TWO, THO

No

sensor characteristics

(See characteristic table in page 101)

are correct

 

Yes

 

 

 

Replace water heat

 

exchange control board

 

 

 

Set water heat board

DPSW11-1 to ON

Place power cable for backup heater

Set breaker for backup heater Manual background to ON, or Check indoor

electronic wiring

Replace backup heater and safety valve

Replace TWI, TWO, Manual background and THO sensors

78

Page 79
Image 79
Toshiba HWS-1402XWHT9-E, HWS-802XWHT6-E, HWS-802H-E, HWS-802XWHM3-E, HWS-1402H-E A05 Error Piping freeze prevention control