Item

 

 

 

Operation flow and applicable data, etc.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8-2.

The following shows the operation modes and controlled objects.

 

 

 

 

 

 

 

 

 

Operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mode and

Operation

 

 

 

 

Heating and Hot water

 

 

Cooling and Hot water

 

 

mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Control Method

 

 

 

Heat pump select

Heat pump select

Heat pump select

Heat pump select

 

 

 

 

 

 

 

 

 

 

Hot

for hot water

for hot water

 

 

 

 

 

for heating

for cooling

 

 

 

Cooling

Heating

water

supply

 

supply

 

 

 

 

 

 

 

 

 

 

 

 

 

only

only

supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hot

 

 

Hot

 

 

Hot

 

 

 

Hot

 

 

 

 

 

only

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating

 

water

Heating

 

water

Cooling

 

water

Cooling

 

water

 

 

Controlled

 

 

 

 

 

 

 

 

 

 

 

 

side

 

supply

side

 

supply

side

 

supply

side

 

supply

 

 

object

 

 

 

 

 

side

 

 

side

 

 

side

 

 

 

side

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat pump

O

O

O

O

 

×

×

 

O

O

 

×

×

 

 

O

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Backup

×

O

×

O

 

×

×

 

×

×

 

×

×

 

 

×

 

 

heater

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hot water

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

cylinder

×

×

O

×

 

O

×

 

O

×

 

O

×

 

 

O

 

 

heater

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

O

Possible

 

 

 

 

 

 

 

 

 

 

 

 

 

 

×

Not possible

1)Hot water supply operation

1)Operation start condition

When the [HOT WATER] remote controller button is pressed and the following operation start condition is met, the operation starts.

TTW < 38°C is detected.

2) Operation mode determination

 

TTW sensor

An operation mode is determined according to the temperature

 

of TTW sensor.

 

 

 

Heat pump operation selection *1 *2

 

 

 

• When TTW < 38°C (a zone in the right figure) is met, the heat

 

 

 

 

pump operation is selected.

(Hot water cylinder unit)

 

Heater operation selection

 

 

 

 

 

When 45°C

 

 

TTW < TSC_H (b zone in the right figure) is

 

 

 

 

met, the heater operation is selected.

 

 

 

Thermostat status "OFF" selection

TTW

 

 

When TTW

 

TSC_H is met, the thermostat status "OFF" is

 

 

 

 

selected.

TSC_H

 

 

 

 

 

 

 

 

 

 

 

c Zone

3) Operation stop

(Temperature set with

Thermostat OFF

remote controller)

 

 

The operation stops in the following cases.

Heater operation

 

The remote controller gives a stop instruction.

 

 

 

b Zone

 

• TTW

 

TSC_H is met.

HP_H OFF 45°C

 

 

 

 

 

 

 

*1: When the outside temperature is -20°C or below, the heater

HP_H ON 38°C

Heat pump

 

operation is selected even if the TTW temperature falls into "a

 

operation

a Zone

zone".

*2: When "Hot water supply" and "Heating" are simultaneously in

 

TSC_H is hot water temperature

 

operation, the heater operation may be selected depending on

 

 

 

set with remote controller

 

the outside air temperature.

 

 

 

 

 

Related FC

 

 

 

 

 

 

 

 

 

 

FC No.

Setting item

Default

Setting available range

 

 

 

 

 

 

 

 

1E

Upper limit of hot water supply temperature

75°C

60-80°C

 

 

 

 

 

 

 

 

1F

Lower limit of hot water supply temperature

40°C

40-60°C

 

 

 

 

 

 

 

 

20

Heat pump start temperature

38°C

20-45°C

 

 

 

 

 

 

 

 

21

Heat pump end temperature

45°C

40-50°C

 

 

 

 

 

 

 

 

24

Outside air correction start temperature for hot water supply*3

0°C

-20-10°C

 

 

25

Outside air correction temperature for hot water supply*3

3 deg

0 -15 deg

 

*3:When the outside temperature is 0°C or below, the boil-up temperature will be higher that setting temperature in hot water supply mode.

39

Page 40
Image 40
Toshiba HWS-802XWHT6-E, HWS-802H-E Operation flow and applicable data, etc, TTW sensor, Hot water cylinder unit