TL [°C]

Item

 

 

 

 

 

 

Operation flow and applicable data, etc.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8-4.

5) Outdoor fan control

 

 

 

 

 

 

 

 

 

Outdoor unit

The outdoor side control part controls the number of fan motor rotations by receiving an operation instruction from the

control

indoor side (Hydro unit) control part.

 

 

 

 

 

 

 

 

* Although the fan motor is a DC motor, which has non-step variable numbers of rotations, it is limited to some steps for convenience of

 

 

 

control.

 

 

 

 

 

 

 

 

 

 

 

 

The number of fan tap rotation allocation [rpm]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W1

W2

W3

W4

W5

W6

W7

W8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

802H-E

 

 

200

230

260

300

340

380

420

460

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1102,

Upper

 

200

240

240

260

320

380

480

500

 

 

 

 

1402H-E

Lower

 

200

200

200

280

360

400

500

520

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W9

WA

WB

WC

WD

WE

WF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

802H-E

 

 

520

570

600

630

670

710

740

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1102,

Upper

 

530

610

640

660

720

780

890

 

 

 

 

 

1402H-E

Lower

 

550

630

660

700

740

820

910

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5-1) Cooling fan control

The TL sensor, TO sensor and operation frequency control the outdoor fan. The control is performed by 1 tap of the DC fan control (14 taps).

For 60 seconds after the start, the maximum fan tap for each zone that is shown in the following table is fixed. After that, the fan is controlled according to the TL sensor temperature.

TL [°C]

58

WE tap

 

55

+ 1 tap/20 secs

38

(Up to the maximum number of rotation for each zone)

Number of rotation hold

35- 1 tap/20 secs

(Up to the minimum number of rotation for each zone)

HWS-802H-E

 

 

Less than 20 Hz

20 Hz or more to less

45 Hz or more

Temperature range

than 45 Hz

 

 

 

 

 

 

 

 

 

 

 

 

Minimum

Maximum

Minimum

Maximum

Minimum

Maximum

 

 

 

 

 

 

 

38°C TO

W6

WC

W8

WE

WA

WE

 

 

 

 

 

 

 

 

29°C

TO < 38°C

W5

WB

W7

WD

W9

WD

 

 

 

 

 

 

 

 

15°C

TO < 29°C

W4

W8

W6

WA

W8

WC

 

 

 

 

 

 

 

 

5°C

TO < 15°C

W3

W6

W5

W8

W7

WA

 

 

 

 

 

 

 

 

0°C

TO < 5°C

W2

W4

W4

W6

W5

W8

 

 

 

 

 

 

 

 

-4°C

TO < 0°C

W2

W3

W3

W5

W4

W6

 

 

 

 

 

 

 

TO < -4°C

OFF

OFF

OFF

W2

OFF

W3

 

 

 

 

 

 

 

TO abnormal

OFF

WC

OFF

WE

OFF

WE

 

 

 

 

 

 

 

 

HWS-1102H-E, 1402H-E

 

 

Less than 20 Hz

20 Hz or more to less

45 Hz or more

Temperature range

than 45 Hz

 

 

 

 

 

 

 

 

 

 

 

 

Minimum

Maximum

Minimum

Maximum

Minimum

Maximum

 

 

 

 

 

 

 

38°C TO

W6

WC

W8

WC

WA

WD

 

 

 

 

 

 

 

 

29°C

TO < 38°C

W5

WB

W7

WC

W9

WC

(WB for 1102)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15°C

TO < 29°C

W4

W8

W6

WA

W8

WC

 

 

 

 

 

 

 

 

5°C

TO < 15°C

W3

W6

W5

W8

W7

WA

 

 

 

 

 

 

 

 

0°C

TO < 5°C

W2

W4

W4

W6

W5

W8

 

 

 

 

 

 

 

 

-4°C

TO < 0°C

W2

W3

W3

W5

W4

W6

 

 

 

 

 

 

 

TO < -4°C

W1

W2

W1

W4

W2

W6

 

 

 

 

 

 

 

TO abnormal

W1

WC

W1

WC

W2

WD

 

 

 

 

 

 

 

 

59