[F03] Error TC sensor failure

Start

 

 

 

TC sensor

No

connector (CN203) is

 

connected

 

Yes

 

TC sensor

No

resistance characteristic

 

is normal

 

Yes

 

Replace water heat exchange control board

[F04] Error TD sensor failure

Start

 

 

 

TD sensor

No

connector (CN603) is

 

connected

 

Yes

 

TD sensor

No

resistance characteristic

 

is normal

 

Yes

 

Replace water heat exchange control board

[F06] Error TE sensor failure

Start

 

 

 

TE sensor

No

connector (CN601) is

 

connected

 

Yes

 

TE sensor

No

resistance characteristic

 

is normal

 

Yes

 

Replace water heat exchange control board

Correct TC sensor connection

Replace TC sensor

Correct TD sensor connection

Replace TD sensor

Correct TE sensor connection

Replace TE sensor