Toshiba HWS-1501CSHM3-E(-UK), HWS-802H-E F03 Error TC sensor failure, F04 Error TD sensor failure

Models: HWS-1402XWHT9-E HWS-1402XWHM3-E HWS-1402XWHT6-E HWS-1501CSHM3-E(-UK) HWS-1402H-E HWS-2101CSHM3-E(-UK) HWS-3001CSHM3-E(-UK) HWS-802XWHM3-E HWS-802H-E HWS-802XWHT6-E

1 168
Download 168 pages 43.83 Kb
Page 86
Image 86
[F03] Error TC sensor failure

[F03] Error TC sensor failure

Start

 

 

 

TC sensor

No

connector (CN203) is

 

connected

 

Yes

 

TC sensor

No

resistance characteristic

 

is normal

 

Yes

 

Replace water heat exchange control board

[F04] Error TD sensor failure

Start

 

 

 

TD sensor

No

connector (CN603) is

 

connected

 

Yes

 

TD sensor

No

resistance characteristic

 

is normal

 

Yes

 

Replace water heat exchange control board

[F06] Error TE sensor failure

Start

 

 

 

TE sensor

No

connector (CN601) is

 

connected

 

Yes

 

TE sensor

No

resistance characteristic

 

is normal

 

Yes

 

Replace water heat exchange control board

Correct TC sensor [F04] Error TD sensor failure connection

[F06] Error TE sensor failure Replace TC sensor

Correct TD sensor Manual background connection

Manual background Replace TD sensor

Correct TE sensor Manual background connection

Replace TE sensor

85

Page 86
Image 86
Toshiba HWS-1501CSHM3-E(-UK) F03 Error TC sensor failure, F04 Error TD sensor failure, F06 Error TE sensor failure