Toshiba HWS-1501CSHM3-E(-UK), HWS-802XWHT6-E, HWS-802H-E, HWS-802XWHM3-E Exchange parts name

Models: HWS-1402XWHT9-E HWS-1402XWHM3-E HWS-1402XWHT6-E HWS-1501CSHM3-E(-UK) HWS-1402H-E HWS-2101CSHM3-E(-UK) HWS-3001CSHM3-E(-UK) HWS-802XWHM3-E HWS-802H-E HWS-802XWHT6-E

1 168
Download 168 pages 43.83 Kb
Page 136
Image 136
Manual background

No.

Exchange parts name

Work procedure

Remarks

 

 

 

 

17

Water heat

 

 

• Close the water piping source valve and the valve

 

 

exchanger assembly

 

 

of water pipe connected to the hydro unit, and

Water

 

 

 

 

then remove the refrigerant and water piping.

 

 

piping fixing

 

 

 

Perform refrigerant recovery with the outdoor unit.

Disconnect all the power source cable, outdoor unit connection cable, and cylinder connection cable.

1.How to remove

1)Perform the step 1-1, step 5, 6, and 8. 2)Remove the water pipe fixing board.

 

(ST2T Ø4 × 8, 2 screws)

 

 

3)Remove the refrigerant piping fixing board.

Refrigerant piping

 

(ST2T Ø4 × 8, 3 screws)

 

4)Remove the nut of the heater connection.

fixing board

 

5)Remove the fixed screws of the electric parts box

 

 

fixing board.

 

 

(ST2T Ø4 × 8, 4 screws)

 

 

6)Remove the side reinforcing board (left).

Nut

 

(ST2T Ø4 × 8, 6 screws) 3 for inside, 3 for outside

 

 

7)Remove the water heat exchanger fixing band.

 

 

(ST2T Ø4 × 8, 6 screws)

 

 

8)Remove the water heat exchanger assembly.

Electric parts

 

 

 

 

 

 

box fixing

 

The heater connection uses a packing for water

 

 

 

 

 

seal. Be careful not to scratch the packing;

 

 

 

otherwise, water leakage may occur.

 

 

 

 

 

 

2. How to attach

 

 

1)Attach a new water heat exchanger assembly in the

Side reinforcing board (left)

 

reverse order of the removal.

 

 

2)Restore all piping and wiring as in the original state,

 

 

and check that there is no water or refrigerant

 

 

leakage.

 

After the water heat exchanger assembly replacement repair, open the water supply source valve and water piping source valve to pass water through the hydro unit, and check that the connection has no water leakage.

After connecting the refrigerant pipe, check that the connection has no refrigerant leakage.

Water heat exchanger fixing band

The piping structure slightly differs in 14kW and 8kW specifications.

Water heat exchanger assembly

135

Page 136
Image 136
Toshiba HWS-1501CSHM3-E(-UK), HWS-802XWHT6-E, HWS-802H-E, HWS-802XWHM3-E, HWS-3001CSHM3-E(-UK) Exchange parts name