(3)Special operation for maintenance and inspection (SW801, SW804)
SW801 and SW804 can perform the following special operations for maintenance and inspection.
1)Switches the dip switch SW804. (See the table below)
2)Presses the
3)Starts the functions shown below. During the start processing of each function, LED D805 (Green) blinks.
4)When the
<Special operation>
SW804
SW804
|
| 4 |
|
| |
|
| 3 |
|
| |
|
| 2 |
ON |
| |
| 1 | |
|
|
SW804
|
| 4 |
|
| |
|
| 3 |
|
| |
|
| 2 |
ON |
| |
| 1 | |
|
|
SW804
|
| 4 |
|
| |
|
| |
|
| 3 |
|
| |
|
| 2 |
ON |
| |
| 1 | |
|
|
Operation when press button switch SW801 is pressed
Refrigerant recovery operation
The outdoor unit operates cooling. The hydro unit may freeze with this operation alone. Remove beforehand the water in the hydro unit. (See
Hydro unit cooling request
Performs a trial cooling operation. (See Note1)
Hydro unit heating request
Performs a trial heating operation.(See Note1)
SW804
|
| 4 |
|
| |
|
| |
|
| 3 |
|
| |
|
| 2 |
ON |
| |
| 1 | |
|
|
SW804
|
| 4 |
|
| |
|
| 3 |
|
| |
|
| 2 |
ON |
| |
| 1 | |
|
|
SW804
|
| 4 |
|
| |
|
| 3 |
|
| |
|
| 2 |
ON |
| |
| 1 | |
|
|
SW804
|
| 4 |
|
| |
|
| |
|
| 3 |
|
| |
|
| 2 |
ON |
| |
| 1 | |
|
|
SW804
|
| 4 |
|
| |
|
| |
|
| 3 |
|
| |
|
| 2 |
ON |
| |
| 1 | |
|
|
SW804
|
| 4 |
|
| |
|
| 3 |
|
| |
|
| 2 |
ON |
| |
| 1 | |
|
|
Fan motor forcible operation
Forcibly performs a fan motor operation.
When SW801 is pressed again or after 2 minutes, the operation returns to the normal control.
(No operation particularly)
PMV full open operation
Fully opens PMV (Pulse motor valve).
When SW801 is pressed again or after 2 minutes, the operation returns to the normal control.
PMV full close operation
Fully closes PMV (Pulse motor valve).
When SW801 is pressed again or after 2 minutes, the operation returns to the normal control.
PMV half open operation
Half opens (250 pulses) PMV (Pulse motor valve).
When SW801 is pressed again or after 2 minutes, the operation returns to the normal control.
When SW801 is pressed again or after 2 minutes, the operation returns to the normal control.
Caution:
Do not connect the coil into the body when perform this operation.
Caution: Although these controls are available during an operation, basically perform them when no operation is in progress. Performing these controls during an operation may cause dangerously rapid pressure change.
125