[A02] Error Temperature rise and error short circuit

Start

TWI, TWO, and THO

sensor characteristics are correct

Yes

(TWI,TWO,THO Manual background70°C)

No

Replace TWI, TWO, Manual background and THO sensors

Flow switch is normal

No

 

 

Yes

 

 

Water outlet

No

temperature is 70°C

 

 

 

 

or higher

 

 

Yes

 

 

Hot water from

Yes

 

boiler or other circuits does

 

 

 

not come in

 

 

No

 

 

Manual background Replace flow switch

Correct water circuit Manual background (To prevent hot water of

other circuits from entering)

Backup heater is energized

Yes

Failure of backup heater Manual background (Too large heater input, thermostat short circuit)

(Measure heater current) Manual backgroundNoManual background

Replace water heat exchange control board

Replace heater unit