Toshiba HWS-1501CSHM3-E(-UK), HWS-802XWHT6-E, HWS-802H-E, HWS-802XWHM3-E, HWS-1402H-E Specifications

Models: HWS-1402XWHT9-E HWS-1402XWHM3-E HWS-1402XWHT6-E HWS-1501CSHM3-E(-UK) HWS-1402H-E HWS-2101CSHM3-E(-UK) HWS-3001CSHM3-E(-UK) HWS-802XWHM3-E HWS-802H-E HWS-802XWHT6-E

1 168
Download 168 pages 43.83 Kb
Page 16
Image 16
Specifications

3

Specifications

 

 

 

 

 

 

 

 

 

Unit name

 

Hydro unit

 

HWS-802XWHM3-E, 802XWHT6-E

 

 

 

 

 

 

 

 

Outdoor unit

 

HWS-802H-E

 

 

 

 

 

 

 

Heating capacity *1 (kW)

 

 

8.0

 

 

 

 

 

 

Cooling capacity *2 (kW)

 

 

6.0

 

 

 

 

 

Variable range of compressor frequency

 

10 - 70 Hz

 

 

 

 

 

 

Power source

 

 

 

Single phase 50Hz 230V

 

 

 

 

 

Operation mode

 

 

Heating

 

Cooling

 

 

 

 

 

 

Electric characteristic *1 *2

Hydro unit

Current (A)

0.98

 

0.46

 

 

 

 

 

 

 

 

 

 

Power (kW)

0.101

 

0.097

 

 

 

 

 

 

 

 

 

 

Power factor (%)

91.5

 

91.7

 

 

 

 

 

 

 

 

 

Outdoor unit

Current (A)

8.26

 

8.90

 

 

 

 

 

 

 

 

 

 

Power (kW)

1.859

 

2.033

 

 

 

 

 

 

 

 

 

 

Power factor (%)

97.8

 

99.3

 

 

 

 

 

 

 

 

 

Total

Starting current (A)

9.24

 

9.36

 

 

 

 

 

 

Operating noise *1 *2 *4

Hydro unit (dB(A))

 

29

 

29

 

 

 

 

 

 

 

 

 

Outdoor unit (dB(A))

 

49

 

49

 

 

 

 

 

 

Coefficient of performance *1 *2

 

 

4.08

 

2.82

 

 

 

 

 

 

 

Hydro unit

 

Outer dimension

Height (mm)

925

 

 

 

 

 

 

 

 

 

 

Width (mm)

525

 

 

 

 

 

 

 

 

 

 

Depth (mm)

355

 

 

 

 

 

 

 

 

 

 

Net weight (kg)

 

50

 

 

 

 

 

 

 

 

Color

 

Silky shade (Munsell 1Y8.5/0.5)

 

 

 

 

 

 

 

 

 

Remote controller

Height (mm)

120

 

 

 

Outer dimension *3

 

 

 

 

 

 

Width (mm)

120

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Depth (mm)

20

 

 

 

 

 

 

 

 

 

Circulating pump

Motor output (W)

125 (MAX)

 

 

 

 

 

 

 

 

 

 

 

Flow rate (L/min)

22.9

 

17.2

 

 

 

 

 

 

 

 

 

Type

Non-self-suction centrifugal pump

 

 

 

 

 

 

 

 

Heat exchanger

 

Plate-type heat exchange

 

 

 

 

 

 

 

Outdoor unit

 

Outer dimension

Height (mm)

890

 

 

 

 

 

 

 

 

 

 

Width (mm)

900

 

 

 

 

 

 

 

 

 

 

Depth (mm)

320

 

 

 

 

 

 

 

 

 

 

Net weight (kg)

 

63

 

 

 

 

 

 

 

 

Color

 

Silky shade (Munsell 1Y8.5/0.5)

 

 

 

 

 

 

 

 

 

Compressor

Motor output (W)

1400

 

 

 

 

 

 

 

 

 

Type

Twin rotary type with DC-inverter variable speed control

 

 

 

 

 

 

 

 

 

Model

DA220A2F-22L

 

 

 

 

 

 

 

 

 

Fan motor

Standard air capacity (m3/min)

50.0

 

 

 

 

Motor output (W)

60

 

 

 

 

 

 

Refrigerant piping

Connection method

 

Flare connection

 

 

 

 

 

 

 

 

 

Hydro unit

Liquid

Ø9.52

 

 

 

 

 

 

 

 

 

 

Gas

Ø15.9

 

 

 

 

 

 

 

 

 

Outdoor unit

Liquid

Ø9.52

 

 

 

 

 

 

 

 

 

 

Gas

Ø15.9

 

 

 

 

 

 

 

 

 

 

Maximum length (m)

 

30

 

 

 

 

 

 

 

 

Maximum chargeless length (m)

30

 

 

 

 

 

 

 

 

Maximum height difference (m)

±30

 

 

 

 

 

 

 

 

 

Minimum length (m)

 

5

 

 

 

 

 

 

 

Refrigerant

 

Refrigerant name

 

R410A

 

 

 

 

 

 

 

 

 

Charge amount (kg)

 

1.8

 

 

 

 

 

 

 

Water piping

 

Pipe diameter

 

R1 1/4

 

 

 

 

 

 

 

 

 

Maximum length (m)

 

None (Need the flow rate 17.5

/min or more)

 

 

 

 

 

 

 

Maximum height difference (m)

±7

 

 

 

 

 

 

 

 

Maximum working water pressure (kPa)

300

 

 

 

 

 

 

Operating temperature range

Hydro unit (°C)

 

5-32

 

 

 

 

 

 

 

 

 

Outdoor unit (°C)

 

-20-43

 

 

 

 

 

 

Operating humidity range

Hydro unit (%)

 

15-85

 

 

 

 

 

 

 

 

 

Outdoor unit (%)

 

15-100

 

 

 

 

 

Wiring connection

Power wiring

 

3 wires: including ground line (Outdoor unit)

 

 

 

 

 

 

 

Connecting line

 

4 wires: including ground line

 

 

 

 

 

 

 

*1 Heating performance measurement conditions: outside air temperature 7 or 6 °C, water supply temperature 30 °C, outlet temperature 35 °C, refrigerant piping length 7.5 m (no height difference), capacity Manual background 97%, COP Manual background 95%, operating noise Manual background +3 dB

*2 Cooling performance measurement conditions: outside air temperature 35 °C, water supply temperature 12 °C, outlet temperature 7 °C, refrigerant piping length 7.5 m (no height difference), capacity Manual background 97%, COP Manual background 95%, operating noise Manual background +3 dB

*3 • The remote controller should be shipped with the hydro unit.

• Use two 1.5-meter wires to connect the hydro unit with the remote controller.

*4 The outdoor unit operating noise is measured at the point of 1m away from the unit back surface center and 1m high from the ground. The hydro unit operating noise is measured at the point of 1m away from the unit front surface center.

The value of the operating noise varies depending on room structure where the unit is installed.

*5 Do not leave the hydro unit at 5 °C or below.

*6 Check the water piping for leakage under the maximum operating pressure.

15

Page 16
Image 16
Toshiba HWS-1501CSHM3-E(-UK), HWS-802XWHT6-E, HWS-802H-E, HWS-802XWHM3-E, HWS-3001CSHM3-E(-UK), HWS-1402H-E Specifications