[A04] Error Freeze prevention control

When the outside temperature or inlet water temperature is low (approx. 20°C or lower) and the room load is large (operation frequency rating), the freeze prevention control may be activated.

Start

Operation restart

Perform air vent

 

Excess air

 

Yes

inside pump

 

 

No

 

 

Chattering from

Yes

 

flow switch

 

 

No

 

Water heat

exchanger board DP_SW11-1 No is ON

Yes

Backup

heater terminal has No 230ACV ( ± 23V)

Yes

Secure water

 

 

 

 

 

Dirt clogging

 

Replace flow switch

circulation amount

 

 

 

inside water circuit

 

 

 

 

 

 

 

 

 

 

 

 

 

(inside strainer, etc)

 

 

 

 

 

 

 

12 M or longer

 

Fit buffer tank and the

 

 

water pipe to

 

second pump

Circulation

 

 

a branch, or 5 or

 

 

 

 

 

flow shortage

 

less branches

 

 

 

 

 

 

 

Set DP_SW11-1 to ON

Power is

No

 

Connect backup heater

connect to backup

heater terminal

 

 

power cable

 

Yes

 

 

 

 

 

 

 

 

 

Set heater breaker to ON

 

 

 

 

 

 

 

 

Check indoor wiring

 

 

 

 

 

Backup

No

 

heater element

 

Replace backup heater unit

is conductive

(Backup heater NG)

 

 

Yes

 

 

TC, TWO, TWI

No

 

Replace TC, TWO,

sensor characteristics

 

 

(See Characteristic table on page 101)

and TWI sensors

are correct

Yes

 

 

 

 

 

Replace water heat

 

 

exchange control board

 

 

 

 

 

 

77

Page 78
Image 78
Toshiba HWS-1402XWHM3-E, HWS-802XWHT6-E, HWS-802H-E, HWS-802XWHM3-E, HWS-3001CSHM3-E(-UK) A04 Error Freeze prevention control