[A11] Error Release protection operation

Start

Flow switch is

normal

No

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace flow switch

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remove sufficiently

 

 

Excess air

Yes

 

 

 

 

excess air

 

 

 

 

 

 

 

 

 

noise comes from

Secure water

 

 

Waste stuck inside

 

Remove waste

 

 

 

 

 

inside pump

 

 

circulation amount

 

 

water circuit

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12 M or longer water

 

Place buffer tank and

 

 

 

 

 

 

 

 

 

 

pipe to a branch,

 

the second pump

Chattering

Yes

 

 

 

 

or 5 or less branches

 

 

 

 

 

 

 

 

Circulation flow

 

 

 

 

 

noise comes from

 

 

 

 

 

 

 

shortage

 

 

 

 

 

flow switch

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

TWI sensor is

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

Attach TWI sensor

attached to pipe

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

TWI and TWO

No

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace TWI or TWO sensor

sensor characteristics

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

are normal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace water heat

 

 

 

 

 

 

 

 

 

exchange control board

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

82

Page 83
Image 83
Toshiba HWS-3001CSHM3-E(-UK) A11 Error Release protection operation, Secure water Waste stuck inside Remove waste