Toshiba HWS-802XWHT6-E F20 Error TFI detach failure, F23 Error Lo pressure sensor detach failure

Models: HWS-1402XWHT9-E HWS-1402XWHM3-E HWS-1402XWHT6-E HWS-1501CSHM3-E(-UK) HWS-1402H-E HWS-2101CSHM3-E(-UK) HWS-3001CSHM3-E(-UK) HWS-802XWHM3-E HWS-802H-E HWS-802XWHT6-E

1 168
Download 168 pages 43.83 Kb
Page 90
Image 90
[F20] Error TFI detach failure

[F20] Error TFI detach failure

Start

TFI sensor

No

is attached to pipe

 

Yes

 

TFI sensor

No

characteristic is normal

(See characteristic table on page 101)

 

Yes

 

TWI sensor

No

characteristic is normal

(See characteristic table on page 101)

 

Yes

 

TWO sensor

No

characteristic is normal

(See characteristic table on page 101)

 

Yes

Replace water heat exchange control board

[F23] Error Lo pressure sensor detach failure

Start

Attach TFI sensor to pipe

[F23] Error Lo pressure sensor detach failure Replace TFI sensor

Manual background Replace TWI sensor

Manual background Replace TWO sensor

Lo pressure sensor

Yes

is detached (CN207, 212)

 

No

 

When operation

No

is stopped, lo pressure sensor

 

is normal *1

 

Yes

 

Replace water heat exchange control board

*1 How to determine: When operation is stopped

Manual background Attach lo pressure sensor

Manual background Replace lo pressure sensor