[F20] Error TFI detach failure

Start

TFI sensor

No

is attached to pipe

 

Yes

 

TFI sensor

No

characteristic is normal

(See characteristic table on page 101)

 

Yes

 

TWI sensor

No

characteristic is normal

(See characteristic table on page 101)

 

Yes

 

TWO sensor

No

characteristic is normal

(See characteristic table on page 101)

 

Yes

Replace water heat exchange control board

[F23] Error Lo pressure sensor detach failure

Start

Attach TFI sensor to pipe

Replace TFI sensor

Replace TWI sensor

Replace TWO sensor

Lo pressure sensor

Yes

is detached (CN207, 212)

 

No

 

When operation

No

is stopped, lo pressure sensor

 

is normal *1

 

Yes

 

Replace water heat exchange control board

*1 How to determine: When operation is stopped

Attach lo pressure sensor

Replace lo pressure sensor

89

Page 90
Image 90