Diagnostic functional operation

 

 

Number of

 

Check

 

 

 

Determination and action

abnormalities

Detailed

 

 

 

code

 

Backup

Automat

for

item

Operational cause

 

 

present

ic reset

 

confirmation

 

 

 

 

 

 

 

 

 

 

 

 

 

TFI sensor error

 

 

1. Check the resistance value and

 

 

F17

Open or short circuit in the floor

×

O

disconnection of the floor-inlet

1

87

 

temperature sensor.

 

 

temperature sensor (TFI).

 

 

 

 

 

 

 

 

 

 

THO sensor error

 

 

1. Check the resistance value and

 

 

F18

Open or short circuit in the heater outlet

×

O

disconnection of the heater outlet

1

88

 

temperature sensor.

 

 

temperature sensor (THO).

 

 

 

 

 

 

 

 

 

 

Detection of THO disconnection error

 

 

1. Check for any disconnection of the

 

 

F19

When TWO–THO>15K is detected and

×

×

heater outlet temperature sensor

1

88

 

30 sec elapsed.

 

 

(THO).

 

 

 

 

 

 

 

 

 

 

TFI sensor error

 

 

1. Check any disconnection of the

 

 

F20

When TWO–TFI>30K is detected and

×

×

1

89

floor-inlet temperature sensor (TFI).

 

TFI<TWI–5K is detected.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low pressure sensor error

 

 

1. Check for any disconnection (body

 

 

 

When PS<0.07 MPa is detected for 2

 

 

or connection wiring) of the low

 

 

F23

sec or more.

O

O

pressure sensor.

1

89

 

 

 

 

 

 

 

 

 

 

2. Check the resistance value of the

 

 

 

 

 

 

low pressure sensor.

 

 

 

 

 

 

 

 

 

 

EEROM error

 

 

1. Replace the water heat exchange

 

 

F29

Inconsistency is detected once without

×

×

1

90

control board.

 

verify ACK after writing to EEPROM.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F30

Extended IC error

×

×

1. Replace the water heat exchange

1

90

When the extended IC is abnormal.

control board.

 

 

 

 

 

 

 

 

 

 

 

 

L07

Communication error

×

×

1. Replace the water heat exchange

1

90

Individual hydro units have a group line.

control board.

 

 

 

 

 

 

 

 

 

 

 

 

 

Communication error

 

 

1. Check the setting of the FC01

 

 

L09

The capability of the hydro unit has not

×

×

capability specifications.

1

90

been set.

HWS-802xx-E = 0012

 

 

 

 

 

 

 

 

 

HWS-1402xx-E = 0017

 

 

 

 

 

 

 

 

 

 

Setting error

 

 

 

 

 

L16

When ZONE1 has not been set, while

×

×

1. Check the body DP-SW12_2,3.

1

90

 

ZONE2 has been set.

 

 

 

 

 

 

 

 

 

 

 

 

69

Page 70
Image 70