Diagnostic functional operation

 

 

Number of

 

Check

 

 

 

Determination and action

abnormalities

Detailed

 

 

 

code

 

Backup

Automat

for

item

Operational cause

 

 

present

ic reset

 

confirmation

 

 

 

 

 

 

 

 

 

 

 

 

 

High pressure protection operation

 

 

1. Check that the service valve is fully

 

 

 

When an abnormal stop occurs due to

 

 

open.

 

 

 

the high pressure release control.

 

 

2. Defect of the pulse motor valve.

 

 

 

When the heat exchange temperature

 

 

3. Check the outdoor fan system

 

 

P20

sensor (TL) detects 63°C during the

O

×

(including clogging).

10

97

 

 

4. Over-filling of refrigerant.

 

cooling operation.

 

 

 

 

 

When the water outlet sensor (TWO)

 

 

5. Check the resistance value of the

 

 

 

detects 60°C during the heating or hot

 

 

heat exchange temperature sensor

 

 

 

 

 

 

 

 

 

water supply operation.

 

 

(TL) and the water outlet

 

 

 

 

 

temperature sensor (TWO).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor fan system error

 

 

1. Check the lock status of the motor

 

 

 

When a DC fan rotor position detection

 

 

fan.

 

 

P22

NG, element short circuit, loss of

O

×

2. Check the connection of the fan

1-4

98

synchronization, or abnormal motor

motor cable connector.

 

 

 

 

 

 

 

 

 

 

 

 

current occurs.

 

 

3. Check the power supply voltage

 

 

 

 

 

 

 

 

 

 

 

 

(AC230 V±23 V).

 

 

 

 

 

 

 

 

 

 

Short circuit of the compressor driver

 

 

1. P26 abnormality occurs when

 

 

 

element error

 

 

operating with the compressor

 

 

 

When an abnormal short circuit of IGBT

 

 

wiring disconnected … Check the

 

 

 

 

 

control board.

 

 

P26

is detected.

O

×

8

98

2. No abnormality occurs when

 

 

 

 

 

 

 

 

 

 

operating with the compressor

 

 

 

 

 

 

wiring disconnected … Compressor

 

 

 

 

 

 

rare short.

 

 

 

 

 

 

 

 

 

 

Compressor rotor position error

 

 

1. Even if the connection lead wire of

 

 

 

The rotor position in the compressor

 

 

the compressor is disconnected, it

 

 

 

cannot be detected.

 

 

stops due to an abnormality in the

 

 

 

 

 

position detection … Replace the

 

 

P29

 

O

×

8

98

 

inverter control board.

 

 

 

 

 

 

 

 

 

 

2. Check the wire wound resistor of the

 

 

 

 

 

 

compressor. Short circuit

 

 

 

 

 

 

… Replace the compressor.

 

 

 

 

 

 

 

 

 