9-3. Outline of the determination diagram

9-3. Outline of the determination diagram

The first determination of whether a defective part is in the hydro unit or the outdoor unit can be performed by the following method.

9-3-1. Procedure of defect diagnosis

In the case of a defect, please apply the following procedure in order to find the defective part.

Confirm the check

Defect Manual background code on the remote control display

Check code

Yes

 

Defect in Hydro unit

A01-A12

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

Check

code

Yes

Abnormality in the

L07-

L16

 

 

communication or setting

 

 

 

 

system

 

No

 

 

 

 

 

 

 

 

 

 

 

 

Check

code

Yes

Abnormality in the water

heat exchange or outdoor

FXX

 

 

 

 

unit sensor system

 

 

 

 

 

No

 

 

 

 

 

 

 

Abnormality in the outdoor unit or hot-water tank unit

9-3-2. How to determine from the check code on the remote control

If the defect is limited by the check code displayed on the remote control, please repair the defect based on the table on the next page.

The check codes are separated into two groups: software and hardware errors.

Since a hardware error cannot be cancelled without a part replacement etc., please perform a repair.

If its abnormality is determined, the abnormality is noticed by indicating the check code on the remote control check code display part while letting off a buzzer.

Manual backgroundManual backgroundManual background Check code display part

9-3-3. How to cancel a check code on the remote controller

(1)Press ZONE1,2 or HOT WATER button (on the operation side) to clear the check code.

(2)Press CL to stop a buzzer for an abnormality only.

Although the above procedure cancels the check code, the hardware error will be displayed again until the hardware repair is completed.