Toshiba HWS-2101CSHM3-E(-UK) Exchange parts, Work procedure, Remarks, Positioning, Motorized

Models: HWS-1402XWHT9-E HWS-1402XWHM3-E HWS-1402XWHT6-E HWS-1501CSHM3-E(-UK) HWS-1402H-E HWS-2101CSHM3-E(-UK) HWS-3001CSHM3-E(-UK) HWS-802XWHM3-E HWS-802H-E HWS-802XWHT6-E

1 168
Download 168 pages 43.83 Kb
Page 154
Image 154
Recess Pulse motor valve body

No.

Exchange parts

Work procedure

Remarks

name

 

 

 

 

 

 

7

Pulse motor valve coil 1. How to remove

 

 

 

1)Perform the step 1-1.

Recess Pulse motor valve body

 

 

2)Remove the coil from the pulse motor valve body

 

 

 

by pulling upward while rotating the coil.

 

2. How to attach

1)Fix the coil by exactly adjusting the coil positioning projection to the recess of the pulse motor valve body.

 

 

Positioning

Motorized

 

 

projection

control valve coil

 

 

 

 

 

8 Fan guard

1. How to remove

 

 

 

 

1)Perform the step 1-1 and step 2.

Fan guard

Bellmouth

Outlet cabinet

Note

Perform a replacement work on cardboard or cloth to prevent the product from being damaged.

2)Remove the outlet cabinet and put with the fan guard side down.

3)Release the hooks (8 positions) of the fan guard.

2. How to attach

 

1)Press the hooks (8 positions) with hands from the

Hooks

front side to fix them.

Note

Check that all the hooks are fixed to the given positions.

153

Page 154
Image 154
Toshiba HWS-2101CSHM3-E(-UK) Exchange parts, Work procedure, Remarks, Recess Pulse motor valve body, Positioning