Outdoor LED

Check and Action procedure

indication

(No specific description indicates outdoor unit parts.)

 

 

 

 

No code

<Indication 1> <Indication 2>

[Discharge abnormality] Compressor's loss of synchronism due to rapid load change, etc.

 

 

* Although the outdoor LED indicates abnormality, the compressor restarts and no abnormality

 

 

is confirmed.

 

 

* This may occur due to the open phase of the compressor or wiring detach.

[F04]

<Indication 1> <Indication 2> [Discharge temperature sensor (TD) failure]

 

 

 

No

 

 

TD sensor connector

Correct TD sensor

 

 

 

(CN603) is connected

 

connection

 

Yes

 

 

 

 

 

TD sensor resistance characteristic is normal

Yes

Replace outdoor control board

No

See the characteristic table on page 101

Replace TD sensor

[F06]

<Indication 1> <Indication 2>

[Heat exchanger temperature sensor (TE) failure]

TE sensor connector (CN601) is connected

Yes

TE sensor resistance characteristic is normal

Yes

Replace outdoor control board

No

 

Correct TE sensor

 

 

connection

 

 

 

 

No

Replace TE sensor

See the

 

characteristic table

 

 

on page 101

 

[F07]

<Indication 1> <Indication 2>

[Heat exchanger temperature sensor (TL) failure]

TL sensor connector (CN604) is connected

YES

TL sensor resistance characteristic is normal

YES

Replace outdoor control board

No

 

Correct TL sensor

 

 

connection

 

 

 

 

No

Replace TL sensor

See the

 

characteristic table

 

 

on page 101

 

[F08]

<Indication 1> <Indication 2>

[Outside air temperature sensor (TO) failure]

TO sensor connector (CN602) is connected

Yes

TO sensor resistance characteristic is normal

Yes

Replace outdoor control board

No

 

Correct TO sensor

 

 

connection

 

 

 

 

No

Replace TO sensor

See the

 

characteristic table

 

 

on page 101

 