Troubleshooting

Table 28: Tracer™ ZN.520 Unit Controller diagnostics

Diagnostic

Unit Response

Latching/non-

Reset

latching

 

 

 

 

 

 

 

 

 

 

 

 

Fan—DISABLED

 

 

 

Valves—DISABLED

 

 

Invalid Unit Configuration2

Outdoor air damper—DISABLED

Non-latching

Communicated or manual reset

Face bypass damper—DISABLED

 

 

 

 

DX/electric heat—DISABLED

 

 

 

Baseboard heat—DISABLED

 

 

 

 

 

 

 

Fans—ENABLED

 

 

 

Valves—ENABLED

 

 

Normal

Outdoor air damper—ENABLED

Non-latching

Communicated or manual reset

Face bypass damper—ENABLED

 

 

 

 

DX/electric heat—ENABLED

 

 

 

Baseboard heat—ENABLED

 

 

 

 

 

 

Note1: The generic binary output (TB4-1, TB4-2) state is unaffected by all unit diagnostics.

Note2: During manual output test, these diagnostics make the green status LED light in a two-blink pattern. For more information see, Manual Output Test, on page 48 for more information.)

Note3: When the entering water temperature is required but not present, the Tracer™ ZN.520 Unit Controller generates a diagnostic to indicate the sensor loss condition. The controller automatically clears the diagnostic once a valid entering water temperature value is present (non-latching diagnostic). When the entering water temperature sensor fails, the controller prohibits all hydronic cooling operation, but allows the delivery of heat when heating is required. In the COOL mode, all hydronic cooling is locked-out, but normal fan and outdoor air damper operation is permitted.

Note4: These diagnostics are non-latching and automatically reset when the input is present and valid.

Note5: When the outdoor air temperature sensor has failed or is not present, the Tracer™ ZN.520 Unit Controller generates a diagnostic to indicate the sensor loss condition. The controller automatically clears the diagnostic once a valid outdoor air temperature value is present (non-latching diagnostic). When the outdoor air temperature sensor fails or is not present, the controller prohibits economizer operation. A value of Enable or Disable for nviEconEnable overrides these decisions, regardless of the presence of an outdoor air temperature value or failure.For more information see, Interoperability, on page 12 for more information.)For more information see, Data Sharing—LonWorks, on page 46 for more information.)

Translating Multiple Diagnostics

The controller senses and records each diagnostic independently of other diagnostics. It is possible to have multiple diagnostics present simultaneously. The diagnostics are reported in the order they oc- cur.

Resetting

Diagnostics

There are many ways to reset unit diagnostics:

qBy cycling the fan switch from off to any speed setting

Automatically

The Tracer™ ZN.520 Unit Control- ler includes an automatic diagnos- tic reset function. This function attempts to automatically recover a unit when the Low Coil Temper- ature Detection diagnostic occurs. When this diagnostic occurs, the controller responds as defined in

Table 28: Tracer™ ZN.520 Unit Controller

diagnostics.

agnostic occurs.

If a Low Coil Temperature Detec- tion diagnostic recurs within 24 hours after an automatic diagnos- tic reset, you must manually reset the diagnostic. See other possible methods for resetting diagnostics in this section.

Manual output test

The TEST button on the controller may be used either during installa- tion to verify proper end device operation or during troubleshoot-

qAutomatically by the controller

qBy initiating a manual output test at the controller

qBy cycling power to the controller

qBy using a building automation system

qBy using the Rover service tool

After the controller detects the Low Coil Temperature Detection diagnostic, the unit waits 30 min- utes before invoking the automatic diagnostic reset function. The au- tomatic diagnostic reset function clears the Low Coil Temperature Detection diagnostic and attempts to restore the controller to normal operation. The controller resumes normal operation until another di-

ing. When depressed, the Test but- ton, the controller exercises all outputs in a predefined sequence. The first and last steps of the se- quence reset the controller diag- nostics. (See “Manual Output Test” on

page 48.for more information.)

Cycling power

When turned-off, the controller's 24 VAC power, and re-applies

UV-SVP01A-EN

54

Page 60
Image 60
Trane ZN.520, Tracer Unit Ventilator manual Translating Multiple Diagnostics