Trane Tracer Unit Ventilator Troubleshooting, Tracer ZN.520 Unit Controller diagnostics, Reset

Models: Tracer Unit Ventilator ZN.520

1 78
Download 78 pages 280 b
Page 59
Image 59
Manual background

Troubleshooting

Table 28: Tracer™ ZN.520 Unit Controller diagnostics

Diagnostic

Unit Response

Latching/non-

Reset

latching

 

 

 

 

 

 

 

 

 

 

 

 

Fan—ENABLED

 

 

 

Valves—ENABLED

 

 

Humidity Input Failure4

Outdoor air damper—ENABLED

Non-latching

Communicated or manual reset

Face bypass damper—ENABLED

 

 

 

 

DX/electric heat—ENABLED

 

 

 

Baseboard heat—ENABLED

 

 

 

 

 

 

 

Fan—ENABLED

 

 

 

Valves—ENABLED

 

 

CO2 Sensor Failure4

Outdoor air damper—ENABLED

Non-latching

Communicated or manual reset

Face bypass damper—ENABLED

 

 

 

 

DX/electric heat—ENABLED

 

 

 

Baseboard heat—ENABLED

 

 

 

 

 

 

 

Fan—ENABLED

 

 

 

Valves—ENABLED

 

 

Generic AIP Failure4

Outdoor air damper—ENABLED

Non-latching

Communicated or manual reset

Face bypass damper—ENABLED

 

 

 

 

DX/electric heat—ENABLED

 

 

 

Baseboard heat—ENABLED

 

 

 

 

 

 

 

Fan—ENABLED

 

 

 

Valves—ENABLED

 

 

Defrosting - Cmpr Lockout4

Outdoor air damper—ENABLED

Non-latching

Communicated or manual reset

Face bypass damper—ENABLED

 

 

 

 

DX/electric heat—OFF

 

 

 

Baseboard heat—ENABLED

 

 

 

 

 

 

 

Fan—ENABLED

 

 

 

Valves—ENABLED

 

 

Maintenance Required

Outdoor air damper—ENABLED

Non-latching

Communicated or manual reset

Face bypass damper—ENABLED

 

 

 

 

DX/electric heat—ENABLED

 

 

 

Baseboard heat—ENABLED

 

 

 

 

 

 

 

Fan—ENABLED

 

 

 

Valves—ENABLED

 

 

Local Fan Mode Failure4

Outdoor air damper—ENABLED

Non-latching

Communicated or manual reset

Face bypass damper—ENABLED

 

 

 

 

DX/Electric Heat—ENABLED

 

 

 

Baseboard heat—ENABLED

 

 

 

 

 

 

 

Fan—ENABLED

 

 

 

Valves—ENABLED

 

 

Local Setpoint Failure4

Outdoor air damper—ENABLED

Non-latching

Communicated or manual reset

Face bypass damper—ENABLED

 

 

 

 

DX/electric heat—ENABLED

 

 

 

Baseboard heat—ENABLED

 

 

 

 

 

 

 

Fan—ENABLED

 

 

 

Valves—ENABLED

 

 

Generic Temperature

Outdoor air damper—ENABLED

Non-latching

Communicated or manual reset

Failure

Face bypass damper—ENABLED

 

 

 

DX/electric heat—ENABLED

 

 

 

Baseboard heat—ENABLED

 

 

 

 

 

 

UV-SVP01A-EN

53

Page 59
Image 59
Trane Tracer Unit Ventilator Troubleshooting, Tracer ZN.520 Unit Controller diagnostics, Diagnostic, Unit Response, Reset