Installation and Wiring

Analog Inputs

Table 6: Analog inputs

 

 

 

Description

Terminals

Function

Range

Zone

TB3-1

Space temperature input

5° to 122°F

 

 

 

(-15°to 50°C)

Ground

TB3-2

Analog ground

NA

Set

TB3-3

Setpoint input

40 ° to 115 °F

 

 

 

(4.4° to 46.1°C)

Fan

TB3-4

Fan switch input

4821 to 4919 Ω (Off)

 

 

 

2297 to 2342 Ω (Auto)

 

 

 

10593 to 10807 Ω (Low)

 

 

 

13177 to 13443 Ω (Medium)

 

 

 

15137 to 16463 Ω (High)

Ground

TB3-6

Analog ground

NA

Analog Input 1

J3-1

Entering water temperature

-40°to 212°F (-40°to 100° C)

 

J3-2

Analog ground

NA

Analog Input 2

J3-3

Discharge air temperature

-40°to 212°F (-40°to 100° C)

 

J3-4

Analog ground

NA

Analog Input 3

J3-5

Outdoor air temperature / Generic

-40°to 212°F (-40°to 100° C)

 

 

temperature

 

 

J3-6

Analog ground

NA

Analog Input 4

J3-7

Power port

4-20 mA

 

J3-8

Universal input

 

 

 

Generic 4-20ma

0 – 100%

 

 

Humidity

0 – 100%

 

 

CO2

0 – 2000ppm

 

J3-9

Analog ground

NA

UV-SVP01A-EN

21

Page 18
Image 18
Trane ZN.520, Tracer Unit Ventilator manual Analog Inputs, Analog inputs