Appendix—Binary

Configuration

Binary Configuration

Table 38: Binary configuration details

Binary input or output

BI 1

BI 2

BI 3

BI 4

Defrost

J1-1

J1-2

J1-3

TB4-1 and TB4- 2

Function

Low temp detection

Condensate overflow

Occupancy

Fan status2

Defrost

Fan high

Fan Medium\Exhust

Fan low

Generic binary output/base board heat

Configuration

Normally closed

Normally closed

Normally closed

Normally open

Normally open

NA

Normally open

Normally open

Normally open

Normally open

Description

Closed: BIP 1 is Normal (no diagnostic)

Open: BIP 1 is Active (diagnostic)

Closed: BIP 2 is Normal (no diagnostic)

Open: BIP 2 is Active (diagnostic)

Closed: BIP 3 is Normal (Occupied)

Open: BIP 3 is Active (Unoccupied)1

Open: BIP 3 is Normal (Occupied)

Closed: BIP 3 is Active (Unoccupied)1

When the controller commands the fan on and the binary input remains open for one minute, BIP is normal (diagnostic).

When the controller commands the fan on and the binary input closes, BIP is active (no diagnostic).

When input is Open, BIP is Active (Defrost activated)

When input is Closed, BIP is Normal (no Defrost)

De-energized: Fan off

Energized: Fan high

De-energized: Fan\Exhaust off

Energized: Fan Medium\Exhust on

De-energized: Fan off

Energized: Fan low

De-energized: Output off (de-energized)

Energized: Output on (energized)

1.The occupancy input applications vary for standalone and communicated instances. For more information, see Occupancy arbitration tables in the Appendix.

2.The fan status device is normally closed during normal fan operation. When the fan is off either from a fan failure or the controller commanding the fan off, the binary input device opens.

UV-SVP01A-EN

61

Page 67
Image 67
Trane Tracer Unit Ventilator Appendix-Binary Configuration, Binary configuration details Binary input or output, Function