Standard End Devices

Table 2: End Device Specifications

Device

Outside Air Actuator

Face and Bypass Actuator

2-way Control Valve

Characteristic

Description

Ambient Temperature Rating

Power Consumption

Torque

Drive Time

Description

Ambient Temperature Rating

Power Consumption

Torque

Drive Time

Description

Ambient Temperature Rating Drive Time

Max Pressure

Close Off

Description

Three-point floating with spring return

-25°F to 125°F 5 VA

35 in-lbs.

90 seconds, 95 degree stroke

Three-point floating 32°F to 122°F

3 VA

35 in-lbs.

80-110 seconds, 95 degree stroke

Three-point modulating

140°F at 95% relative humidity

50seconds

400 psi water

Varied by size and Cv

Temperature

Water 200°F maximum

14

UV-SVP01A-EN

Page 11
Image 11
Trane Tracer Unit Ventilator, ZN.520 manual Standard End Devices