Troubleshooting
Table 31: Valves stay open
Probable cause | Possible Explanation |
|
|
| When the fan is off with no demand for capacity (0%) and the outdoor air temperature is below the |
Freeze avoidance | freeze avoidance setpoint, the controller opens the water valves (100%) to prevent coil freezing. This |
| includes unoccupied mode when there is no call for capacity or any other time the fan is off. |
Normal operation
The controller opens and closes the valves to meet the unit capacity requirements.
DX/Electric Heat
Table 32: DX or electric output(s) does not energize
Probable cause | Possible Explanation | |
|
| |
|
| |
Unit wiring | The wiring between the controller outputs and the end devices must be present and correct for normal | |
operation. | ||
| ||
|
| |
Unit configuration | The controller must be properly configured based on the actual installed end devices and application. | |
When the unit configuration does not match the actual end devices, the unit may not work correctly. | ||
| ||
|
| |
Diagnostic present | A specific list of diagnostics affect compressor and electric heat operation. For more information see, | |
Tracer™ ZN.520 Unit Controller diagnostics, on page 52 for more information.) | ||
| ||
|
| |
| The controller includes a manual output test sequence you can use to verify output operation and | |
Manual output test | associated output wiring. However, based on the current step in the test sequence, the DX or electric | |
| outputs may be OFF. For more information see, Manual Output Test, on page 48 for more information.) | |
|
| |
| When the fan is OFF with no demand for capacity (0%) and the outdoor air temperature is below the | |
Freeze avoidance | freeze avoidance setpoint, the controller disables compressors and electric heat outputs. This includes | |
| UNOCCUPIED mode when there is no call for capacity or any other time the fan is OFF. | |
|
| |
Normal operation | The controller energizes the outputs only as needed to meet the unit capacity requirements. | |
|
|
Outside Air Damper
Table 33: Outdoor air damper stays closed
Probable cause |
| Explanation | |
|
| ||
|
| ||
Unit wiring | The wiring between the controller outputs and the outdoor air damper must be present and correct for | ||
normal damper operation. | |||
| |||
|
| ||
| The controller must be properly configured based on the actual installed end devices and application. | ||
Unit configuration | When the unit configuration does not match the actual end devices, the damper may not work | ||
| correctly. | ||
|
| ||
After | |||
remains OFF until the | |||
| |||
|
| ||
| When | ||
| conditions occurs: | ||
1. | The controller exits | ||
| |||
| 2. | The controller exits | |
|
| ||
Diagnostic present | A specific list of diagnostics affects outdoor air operation. For more information see, Tracer™ ZN.520 | ||
Unit Controller diagnostics, on page 52 for more information.) | |||
| |||
|
| ||
| The controller includes a manual output test sequence you can use to verify output operation and | ||
Manual output test | associated output wiring. However, based on the current step in the test sequence, the unit damper | ||
| may not be open. For more information see, Manual Output Test, on page 48 for more information.) | ||
|
| ||
Fan mode OFF | When a local fan mode switch (provided on the Trane zone sensor) determines the fan operation, the | ||
OFF position controls the unit OFF and damper to close. | |||
|
57 |