Trane Tracer Unit Ventilator manual Troubleshooting, Valves stay open, Probable cause, Explanation

Models: Tracer Unit Ventilator ZN.520

1 78
Download 78 pages 280 b
Page 63
Image 63
Table 32: DX or electric output(s) does not energize

Troubleshooting

Table 31: Valves stay open

Probable cause

Possible Explanation

 

 

 

When the fan is off with no demand for capacity (0%) and the outdoor air temperature is below the

Freeze avoidance

freeze avoidance setpoint, the controller opens the water valves (100%) to prevent coil freezing. This

 

includes unoccupied mode when there is no call for capacity or any other time the fan is off.

Normal operation

The controller opens and closes the valves to meet the unit capacity requirements.

DX/Electric Heat

Table 32: DX or electric output(s) does not energize

Probable cause

Possible Explanation

 

 

 

 

Unit wiring

The wiring between the controller outputs and the end devices must be present and correct for normal

operation.

 

 

 

Unit configuration

The controller must be properly configured based on the actual installed end devices and application.

When the unit configuration does not match the actual end devices, the unit may not work correctly.

 

 

 

Diagnostic present

A specific list of diagnostics affect compressor and electric heat operation. For more information see,

Tracer™ ZN.520 Unit Controller diagnostics, on page 52 for more information.)

 

 

 

 

The controller includes a manual output test sequence you can use to verify output operation and

Manual output test

associated output wiring. However, based on the current step in the test sequence, the DX or electric

 

outputs may be OFF. For more information see, Manual Output Test, on page 48 for more information.)

 

 

 

When the fan is OFF with no demand for capacity (0%) and the outdoor air temperature is below the

Freeze avoidance

freeze avoidance setpoint, the controller disables compressors and electric heat outputs. This includes

 

UNOCCUPIED mode when there is no call for capacity or any other time the fan is OFF.

 

 

Normal operation

The controller energizes the outputs only as needed to meet the unit capacity requirements.

 

 

Outside Air Damper

Table 33: Outdoor air damper stays closed

Probable cause

 

Explanation

 

 

 

 

Unit wiring

The wiring between the controller outputs and the outdoor air damper must be present and correct for

normal damper operation.

 

 

 

 

The controller must be properly configured based on the actual installed end devices and application.

Unit configuration

When the unit configuration does not match the actual end devices, the damper may not work

 

correctly.

 

 

Random-start observed

After power-up, the controller always observes a random-start from 5 to 30 seconds. The controller

remains OFF until the random-start time expires.

 

 

 

 

When power-up control wait is enabled (non-zero time), the controller remains OFF until one of two

 

conditions occurs:

Power-up control wait

1.

The controller exits power-up control wait once it receives communicated information.

 

 

2.

The controller exits power-up control wait once the power-up control wait time expires.

 

 

Diagnostic present

A specific list of diagnostics affects outdoor air operation. For more information see, Tracer™ ZN.520

Unit Controller diagnostics, on page 52 for more information.)

 

 

 

 

The controller includes a manual output test sequence you can use to verify output operation and

Manual output test

associated output wiring. However, based on the current step in the test sequence, the unit damper

 

may not be open. For more information see, Manual Output Test, on page 48 for more information.)

 

 

Fan mode OFF

When a local fan mode switch (provided on the Trane zone sensor) determines the fan operation, the

OFF position controls the unit OFF and damper to close.

 

UV-SVP01A-EN

57

Page 63
Image 63
Trane Tracer Unit Ventilator, ZN.520 manual Troubleshooting, Valves stay open, Probable cause, Possible Explanation