Troubleshooting
Table 33: Outdoor air damper stays closed
Probable cause | Explanation | ||
|
|
| |
|
| ||
| You can communicate a desired operating mode (such as OFF, HEAT, and COOL) to the controller. When |
| |
Requested mode OFF | OFF is communicated to the controller, the unit controls the fan OFF. There is no heating or cooling | ||
| (valves are closed). | ||
|
| ||
| When the fan is OFF and the outdoor air temperature is below the freeze avoidance setpoint, the | ||
Freeze avoidance | controller disables economizing and keeps the outdoor air damper closed. This includes UNOCCUPIED | ||
| mode when there is no call for capacity or any other time the fan is OFF. | ||
|
| ||
UNOCCUPIED mode | When the controller is in the UNOCCUPIED mode, the outdoor air damper remains closed unless | ||
economizing is enabled. | |||
| |||
|
| ||
| The controller includes both a morning warm up and | ||
Warm up and | damper closed during the transition from UNOCCUPIED to OCCUPIED. This is an attempt to bring the | ||
| space under control as quickly as possible. | ||
|
| ||
| The controller opens and closes the outdoor air damper based on the controller's occupancy mode and | ||
| fan operation. Normally, the outdoor air damper is open during OCCUPIED, OCCUPIED STANDBY, and | ||
Normal operation | OCCUPIED BYPASS mode when the fan is running and closed during UNOCCUPIED mode unless the | ||
| controller is economizing. For more information see, Modulating Outdoor Air Operation, on page 43 for | ||
| more information.) | ||
|
|
| |
Table 34: Outdoor air damper stays open | |||
|
| ||
Probable Cause | Explanation | ||
|
|
| |
|
|
| |
Unit wiring | The wiring between the controller outputs and the outdoor air damper must be present and correct for | ||
normal damper operation. | |||
| |||
|
| ||
| The controller must be properly configured based on the actual installed end devices and application. | ||
Unit configuration | When the unit configuration does not match the actual end devices, the damper may not work | ||
| correctly. | ||
|
| ||
| The controller includes a manual output test sequence you can use to verify output operation and | ||
Manual output test | associated output wiring. However, based on the current step in the test sequence, the unit damper | ||
| may be open. For more information see, Manual Output Test, on page 48 for more information.) | ||
|
| ||
| The controller opens and closes the outdoor air damper based on the controller's occupancy mode and | ||
| fan operation. Normally, the outdoor air damper is open during OCCUPIED, OCCUPIED STANDBY, and | ||
Normal operation | OCCUPIED BYPASS mode when the fan is running and closed during UNOCCUPIED mode unless the | ||
| controller is economizing. For more information see, Modulating Outdoor Air Operation, on page 43 for | ||
| more information.) | ||
|
|
|