Trane Tracer Unit Ventilator, ZN.520 manual Installation and Wiring, Power

Models: Tracer Unit Ventilator ZN.520

1 78
Download 78 pages 280 b
Page 21
Image 21
Wiring

Installation and Wiring

Wiring

!WARNING

Warning! Disconnect all elec- trical power before servicing unit to prevent injury or death due to electrical shock. Use copper conductors only. The use of aluminum or other incorrect types of wire may result in overheating and equipment damage.

!CAUTION

Caution: To prevent damage to the unit ventilator, refer to the diagram provided on the inside of the unit's access panel for specific wiring infor-

mation. All controls are wired at the factory. Single point power, zone sensor, and communication wiring is to be installed by the contractor.

Important! All wiring must comply with state, local, and federal guidelines. Contact the appropriate local agency for furthur information.

Important! Wires for temperature sensors, communication lines, 24 VAC, and contact closure sensing inputs should not be bundled with or run near high voltage wiring.

qPower wiring must be separated from the Tracer ZN.520 and all low voltage wires. External input wires should be run in separate conduits from high voltage wires.

qWires connected to pin headers should be formed and routed so as to cause minimum strain on the Tracer ZN.520 connector.

qA minimum of 1.5" clearance (from the pin centerline) for wires up to 16 AWG is recommended for bending and forming wires.

qAll sensor and input circuits are at or near ground potential. Do not connect any sensor or input circuit to an external ground connection.

qA close-coupled ground connection is required for the Tracer ZN.520. T

qTable 7: Tracer ZN.520 Wiring Requirements, shows Tracer ZN.520 wire types and lengths.

Table 7: Tracer ZN.520 Wiring Requirements

Application

Wire Type

Length

 

 

 

Contact Closure

18 AWG

Up to

1000 ft.

 

 

24 VAC

16-22 AWG

Up to

1000 ft.

 

 

Thermostat

16-22 AWG

Up to

1000 ft.

 

 

Zone

16-22 AWG

Up to

Sensor

200 ft.

 

Communications

Belden 8760

Up to

 

or equivalent

5000 ft.

Power

The Tracer ZN.520 controller is

powered by 24 VAC. (See Table 7: “Tracer ZN.520 Wiring Require- ments”)A total of two 1/4-inch

quick-connect terminals are pro- vided for 24 VAC connection to the board.

Figure 12: Power connection to the Tracer ZN.520 unit controller

24

UV-SVP01A-EN

Page 21
Image 21
Trane Tracer Unit Ventilator, ZN.520 manual Installation and Wiring, Power