Installation and Wiring

Binary Outputs

Outputs are load side switching tri- acs. The triac acts as a switch, ei- ther making or breaking the circuit between the load (valve, damper, contactor, relay) and ground.

Table 4: Binary outputs

Description

Fan high

Fan medium,

Exhaust fan

Fan low

No connection

Cool open, face bypass cool valve DX, 2-position cooling valve, BI 5

Cool close

Face/bypass damper open

Face/bypass damper close

Heat open

Face bypass isolation valve, 2-position heating valve Electric heat 1st stage

Heat close

Electric heat 2nd stage

Economizer damper open

Economizer damper close

Terminals

Output

Rating

 

J1-1

12 VA

J1-2

12 VA

J1-3

12 VA

J1-4 (Key)

J1-5

12 VA

J1-6

12 VA

J1-7

12 VA

J1-8

12 VA

J1-9

12 VA

J1-10

12 VA

J1-11

12 VA

J1-12

12 VA

Load Energized

Load De-energized

1 VAC RMS

24 VAC RMS

(typical)

(typical)

1 VAC RMS

24 VAC RMS

(typical)

(typical)

1 VAC RMS

24 VAC RMS

(typical)

(typical)

1 VAC RMS

24 VAC RMS

(typical)

(typical)

1 VAC RMS

24 VAC RMS

(typical)

(typical)

1 VAC RMS

24 VAC RMS

(typical)

(typical)

1 VAC RMS

24 VAC RMS

(typical)

(typical)

1 VAC RMS

24 VAC RMS

(typical)

(typical)

1 VAC RMS

24 VAC RMS

(typical)

(typical)

1 VAC RMS

24 VAC RMS

(typical)

(typical)

1 VAC RMS

24 VAC RMS

(typical)

(typical)

Generic/baseboard Heat Binary Output

Table 5: Generic binary outputs

 

 

 

 

Description

Terminals

Output

Load Energized

Load De-energized

 

 

Rating

 

 

Generic/ baseboard heat output

TB4-1

12 VA

1 VAC RMS

24 VAC RMS

 

 

 

(typical)

(typical)

24VAC

TB4-2

12 VA

NA

NA

20

UV-SVP01A-EN

Page 17