Trane Tracer Unit Ventilator Standard End Devices, End Device Specifications Device, Description

Models: Tracer Unit Ventilator ZN.520

1 78
Download 78 pages 280 b
Page 13
Image 13
Humidity Sensor

Standard End Devices

Table 2: End Device Specifications

Device

Humidity Sensor

CO 2 Sensor

Fan Relay

Characteristic

Sensing Element

Sensing Element

Range

Operating Temperature Range Max Supply Voltage

Output Characteristics

Drift Rate

Sensing Element

Range

Operating Temperature Range Supply Voltage

Output Characteristics

Power consumption

Drift Rate

Contact Rating

Terminals

Contact material

Description

Polymer capacitive

Accuracy: ± 5% over 20-95% RH @ 77ºF

0 to 99% RH

0°F to 140ºF

24VDC

4to 20 MA for 0-100% RH

Less than 1% per year

Accuracy: ± 100ppm full scale

0-2000 ppm

59°F to 95ºF

24VAC

0-10 VDC for 0-2000 ppm

10 VA

±5% full scale over four years

20 amps at 120/240 vac 3/4 hp at 120 vac

1 1/2 hp at 240 vac

20 amps @ 28 vdc

DPDT

0.25quick connect Silver-Cadium Oxide

Coil

24 vac 2.7 va

16

UV-SVP01A-EN

Page 13
Image 13
Trane Tracer Unit Ventilator Standard End Devices, End Device Specifications Device, Humidity Sensor CO 2 Sensor Fan Relay