Configuration

Binary Inputs1

Table 11: Binary input summary

Binary input

BI 1

BI 2

BI 3

BI 4

Configuration

Low coil temperature detection or not used

Not used

Occupancy, generic, or not used

Fan status or not used

Valid range

Normally open Normally closed

Normally open Normally closed

Normally open Normally closed

Normally open Normally closed

1. Trane Rover service tool uses the unit type to determine and download the proper default binary input configuration.

Analog Inputs1

Table 12: Analog input summary

Analog input

Zone

Set

Fan

AI 1

AI 2

AI 3

AI 4

Configuration

Space temperature

Setpoint (hardwired)

Fan switch

Entering water temperature

Discharge air temperature

Outdoor air temperature or generic temperature input (Note 2)

Humidity, CO2 or generic 4-20mA input

Calibration range

+/- 10.0°F (0.1°F resolution)

+/- 10.0°F (0.1°F resolution)

NA

NA

NA

NA

NA

1.Trane Rover service tool uses the unit type to determine and download the proper default analog input configuration.

2.Analog input 3 (AI 3) configured as generic temperature input does not affect unit operation. When configured, the Tracer™ ZN .520 Unit

Controller communicates the generic temperature value to Rover or Tracer Summit and displays it as generic temperature.