Trane ZN.520 Standard End Devices, End Device Specifications Device, Characteristic, Description

Models: Tracer Unit Ventilator ZN.520

1 78
Download 78 pages 280 b
Page 12
Image 12
3-way Control Valve

Standard End Devices

Table 2: End Device Specifications

Device

3-way Control Valve

Time clock

Zone sensor

Characteristic

Description

Ambient Temperature Rating Drive Time

Max Pressure

Close Off

Temperature

Size

Power Consumption

Switch

Switch Rating

Minimum Switching Current

Shortest Switching Time

Ambient Temperature Range

Wiring Connections

Backup

Zone Sensor Wiring Size And Maximum Lengths

Description

Three-point modulating

140°F at 95% relative humidity

50seconds 400 psi water

Varied by size and Cv

Water 200°F maximum

2.83'' x 4.0'' x 2.06'' 4.4 VA

SPDT dry contacts, silver cadmium oxide 16A 250V resistive, 1000 Watts tungsten 100mA,230V

1 minute

-14°F to 131°F

Screw terminals suitable for #10 to #24 AWG

Seven day capacitor backup

16-22 AWG: up to 200 feet

UV-SVP01A-EN

15