Trane Diagnostics, Troubleshooting, Tracer ZN.520 Unit Controller diagnostics, Unit Response

Models: Tracer Unit Ventilator ZN.520

1 78
Download 78 pages 280 b
Page 58
Image 58
Diagnostics

Troubleshooting

Diagnostics

Table 28: Tracer™ ZN.520 Unit Controller diagnostics

Diagnostic

Unit Response

Latching/non-

Reset

latching

 

 

 

 

 

 

 

 

 

 

 

 

Fan—OFF

 

Auto reset once within 24hrs. If

 

Valves—OPEN

 

 

 

safety generates a diagnostic

Low Coil Temperature

Outdoor air damper—CLOSED

 

Latching

more than once a communi-

Detect2

Face bypass damper—BYPASS

 

cated or manual reset will be

 

DX/electric heat—OFF

 

 

 

necessary.

 

Baseboard heat—OFF

 

 

 

 

 

 

 

 

 

Fan—OFF

 

 

 

Valves—CLOSED

 

 

Low Air Flow - Fan Failure2

Outdoor air damper—CLOSED

Latching

Communicated or manual reset

Face bypass damper—BYPASS

 

 

 

 

DX/electric heat—OFF

 

 

 

Baseboard heat—OFF

 

 

 

 

 

 

 

Fan—OFF

 

 

 

Valves—CLOSED

 

 

Space Temperature

Outdoor air damper—CLOSED

Non-latching

Communicated or manual reset

Failure2,4

Face bypass damper—BYPASS

 

 

 

DX/electric heat—OFF

 

 

 

Baseboard heat—OFF

 

 

 

 

 

 

 

Fan—ENABLED

 

 

 

Valves—ENABLED3

 

 

Entering Water Temp

Outdoor air damper—ENABLED3

Non-latching

Communicated or manual reset

Failure4

Face bypass damper—ENABLED3

 

 

 

DX/electric heat—ENABLED3

 

 

 

Baseboard heat—OFF

 

 

 

 

 

 

 

Fan—OFF

 

Auto reset once within 24hrs. If

 

Valves—OPEN

 

 

 

safety generates a diagnostic

 

Outdoor air damper—CLOSED

 

Discharge Air Temp Limit2

Latching

more than once a communi-

Face bypass damper—BYPASS

 

 

cated or manual reset will be

 

DX/electric heat—OFF

 

 

 

necessary.

 

Baseboard heat—OFF

 

 

 

 

 

 

 

 

 

Fan—OFF

 

 

 

Valves—CLOSED

 

 

Discharge Air Temp

Outdoor air damper—CLOSED

Non-latching

Communicated or manual reset

Failure2,4

Face bypass damper—BYPASS

 

 

 

DX/electric heat—OFF

 

 

 

Baseboard heat—OFF

 

 

 

 

 

 

 

Fan—ENABLED

 

 

 

Valves—ENABLED

 

 

 

Outdoor air damper—MINIMUM

 

 

Outdoor Air Temp Failure4

POSITION5

Non-latching

Communicated or manual reset

 

Face bypass damper—ENABLED

 

 

 

DX/electric heat—ENABLED

 

 

 

Baseboard heat—ENABLED

 

 

 

 

 

 

UV-SVP01A-EN

52

Page 58
Image 58
Trane manual Diagnostics, Troubleshooting, Tracer ZN.520 Unit Controller diagnostics, Unit Response, Latching/non, Reset