Configuration

Occupied Bypass Timer

Table 18: Bypass timer range

Default

Occupancy bypass timer1

120 Minutes

1. The occupied bypass timer is used for timed override applications.

Valid range

0 to 240 minutes (1 minute resolution)

Power-Up Control Wait

Table 19: Control wait timer

Power up control wait (2 minutes)

Default

120 seconds

Valid range

Disable or enable

Maintenance Timers

Table 20: Maintenance timer range

Default

Maintenance timer

0

Valid range

0 to 10,000 hours

UV-SVP01A-EN

37

Page 34
Image 34
Trane ZN.520, Tracer Unit Ventilator manual Occupied Bypass Timer, Power-Up Control Wait, Maintenance Timers