Trane Tracer Unit Ventilator, ZN.520 manual Input/Output Summary, summary

Models: Tracer Unit Ventilator ZN.520

1 78
Download 78 pages 280 b
Page 27
Image 27
Input/Output Summary

Input/Output Summary

Input/Output Summary

The following lists all possible bi- nary and analog inputs and out- puts available for the classroom unit ventilator applications. Some of the points listed may be mutual- ly exclusive and some are optional. (See Table 8: Input and output

summary)

Table 8: Input and output summary

Most binary inputs and outputs are wired from the factory based on unit configuration and options. If the generic inputs and outputs are to be used, wiring connections are made at the 1/4” quick-connect ter- minals provided.

Analog inputs from a wall-mount- ed zone sensor, humidity sensor, CO2 sensor, or a generic device

must be wired to the 1/4” quick- connect terminals provided. Most other analog inputs will be wired from the factory.

Input

Binary Inputs

Binary Outputs

Description

Freezestat

Fan Status

Occupancy/Generic

J1-1 Fan High Speed

J1-3 Fan Low Speed

J1-2 Exhaust Fan

J1-5 Cooling Open (Modulating valve/DX/ Isolation valve)

J1-6 Cooling Close

J1-7 Face and Bypass Damper

Open

J1-8 Face and Bypass Damper

Close

J1-9 Heat Open (Modulating

valve/Isolation valve) or 1 st

Stage Electric Heat

J1-10 Heat Close or 2 n d Stage

Electric Heat

J1-11 Economizer Damper

Open

J1-12 Economizer Damper

Close

TB4-1 Generic/Baseboard

Heat

TB4-2 24 VAC

30

UV-SVP01A-EN

Page 27
Image 27
Trane Tracer Unit Ventilator, ZN.520 manual Input/Output Summary, summary