Trane Tracer Unit Ventilator Appendix-Unit Operation cont, Application mode input, mode output

Models: Tracer Unit Ventilator ZN.520

1 78
Download 78 pages 280 b
Page 69
Image 69
Appendix—Unit Operation cont.

Appendix—Unit Operation cont.

Table 39: Unit operation based on the effective heat/cool output

Application mode input

Heat/cool mode input

Effective heat/ cool

mode output

(nviApplicMode)

(nviHeatCool)

(nvoHeatCool)

 

 

Cool

Any state

Cool

Pre-cool

Any state

Pre-cool

Off

Any state

Off

Test

Any state

Determined by controller

Fan only

Any state

Fan only

 

 

 

Unit Operation

Fan—Enabled

Heating—Disabled1

Cooling—Enabled

Damper

Fan—Enabled

Heating—Disabled1

Cooling—Enabled

Damper—Disabled

Fan—Disabled

Heating—Disabled

Cooling—Disabled

Damper—Disabled

Fan—Enabled

Heating—Enabled

Cooling—Enabled

Damper—Enabled

Fan—Enabled

Heating—Disabled

Cooling—Disabled

Damper—Enabled

1.Use of heat for supply air tempering and dehumidification remains available.

2.Night purge, Emergency heat, and Nul modes are not supported by the Tracer™ ZN.520 Unit Controller. If one of these modes is received by the controller, it is interpreted as Auto.

UV-SVP01A-EN

63

Page 69
Image 69
Trane Tracer Unit Ventilator, ZN.520 Appendix-Unit Operation cont, Unit operation based on the effective heat/cool output