Trane ZN.520 manual Troubleshooting, Valves stay closed, Probable cause, Possible Explanation

Models: Tracer Unit Ventilator ZN.520

1 78
Download 78 pages 280 b
Page 62
Image 62
Table 30: Valves stay closed

Troubleshooting

Valves

Table 30: Valves stay closed

Probable cause

Possible Explanation

 

 

 

 

Unit wiring

The wiring between the controller outputs and the valve(s) must be present and correct for normal

valve operation.

 

 

 

Random-start observed

After power-up, the controller always observes a random-start from 5 to 30 seconds. The controller

remains off until the random-start time expires.

 

 

 

Unit configuration

The controller must be properly configured based on the actual installed end devices and application.

When the unit configuration does not match the actual end devices, the valves may not work correctly.

 

 

 

 

When power-up control wait is enabled (non-zero time), the controller remains off until one of two

Power-up control

conditions occurs:

wait

The controller exits power-up control wait once it receives communicated information.

 

The controller exits power-up control wait once the power-up control wait time expires.

 

 

Diagnostic present

A specific list of diagnostic affects valve operation. For more information see, Tracer™ ZN.520 Unit

Controller diagnostics, on page 52 for more information.)

 

 

 

 

The controller includes a manual output test sequence you can use to verify output operation and

Manual output test

associated output wiring. However, based on the current step in the test sequence, the valve(s) may not

 

be open. For more information see, Manual Output Test, on page 48 for more information.)

 

 

Fan mode off

When a local fan mode switch (provided on the Trane zone sensor) determines the fan operation, the

off position controls the unit off and valves to close.

 

 

 

 

You can communicate a desired operating mode (such as OFF, HEAT, and COOL) to the controller. When

Requested mode off

OFF is communicated to the controller, the unit controls the fan OFF. There is no heating or cooling

 

(valves are closed).

 

 

 

The controller includes entering water temperature sampling logic which is automatically invoked

 

during 2-pipe and 4-pipe changeover when the entering water temperature is either too cool or too hot

 

for the desired heating or cooling. For more information see, Entering Water Temperature Sampling,

Sampling logic

on page 43 for more information.)

Example: A 2-pipe heat/cool changeover unit will not cool if the entering water temperature is too

 

 

warm for cooling or if the entering water sensor is not present. The unit will not heat if the entering

 

water temperature is too cool for heating. If failed the controller will close valve for one hour then

 

reattempt sampling routine.

 

 

Table 31: Valves stay open

 

 

 

Probable cause

Possible Explanation

 

 

 

 

Unit wiring

The wiring between the controller outputs and the valve(s) must be present and correct for normal

valve operation.

 

 

 

Unit configuration

The controller must be properly configured based on the actual installed end devices and application.

When the unit configuration does not match the actual end devices, the valves may not work correctly.

 

 

 

Diagnostic present

A specific list of diagnostic affects valve operation. For more information see, Tracer™ ZN.520 Unit

Controller diagnostics, on page 52 for more information.)

 

 

 

 

The controller includes a manual output test sequence you can use to verify output operation and

Manual output test

associated output wiring. However, based on the current step in the test sequence, the valve(s) may be

 

open.For more information see, Manual Output Test, on page 48 for more information.)

 

 

 

The controller includes entering water temperature sampling logic which automatically invoked during

Sampling logic

2-pipe and 4-pipe changeover when the entering water temperature is either too cool or too hot for the

desired heating or cooling. For more information see, Entering Water Temperature Sampling, on page

 

 

43 for more information.)

 

 

UV-SVP01A-EN

56

Page 62
Image 62
Trane ZN.520 manual Troubleshooting, Valves stay closed, Probable cause, Possible Explanation, Valves stay open