Trane ZN.520 Standard End Devices, End Device Specifications Device, Characteristic, Description

Models: Tracer Unit Ventilator ZN.520

1 78
Download 78 pages 280 b
Page 10
Image 10
Standard End Devices

Standard End Devices

Table 2: End Device Specifications

Device

Fan Status Switch

Low Temperature Detection Switch (Freezestat)

OutsideAir Sensor/discharge AirSensor/Entering

Water Temperature Sensor/Unit Mounted, Zone

Return-air Temperature Sensor

Characteristic

Material

Operating Temperature Range Contact Form

Preset

Trip Temperature:

Release Temperature

Rating—Auto Reset

Sensing Element

Description

Contact Blade—Pilot duty rated

-40°F/250°F (-40°C/120°C)

SPST-NO

Fan status - 0.07”

36°F ± 2°F (2°C + - 1.11°C)

44°F ± 3°F (6.67°C + - 1.67°C)

Pilot Duty

120

VAC

240

VAC

(24 VAC)

 

 

 

 

FLA

10.0

 

5.0

 

LRA

60.0

 

30.0

 

 

 

 

 

 

Thermistor 10 KOhms @ 77°F ± 1.8°F (25°C ±1°C)

UV-SVP01A-EN