Toshiba HWS-2101CSHM3-E(-UK), HWS-802H-E Operation flow and applicable data, etc, Flow rateL/min

Models: HWS-1402XWHT9-E HWS-1402XWHM3-E HWS-1402XWHT6-E HWS-1501CSHM3-E(-UK) HWS-1402H-E HWS-2101CSHM3-E(-UK) HWS-3001CSHM3-E(-UK) HWS-802XWHM3-E HWS-802H-E HWS-802XWHT6-E

1 168
Download 168 pages 43.83 Kb
Page 54
Image 54
Flow rate(L/min)

Item

 

 

 

 

Operation flow and applicable data, etc.

 

 

 

 

 

 

 

 

 

 

 

8-3.

5) Mixing Valve control (2-temperature heating control)

 

 

Hydro Unit

To set different radiator unit supply temperatures or floor heating supply temperatures, the unit performs Mixing Valve

Control

control.

 

 

 

 

 

 

 

 

 

When Mixing Valve "Yes" is selected, the unit controls Mixing Valve every 4 minutes (FC) based on the difference TSC_Δ

 

T between the Zone2 set temperature and TFI (floor inlet water temperature sensor) temperature as follows:

 

 

 

 

 

 

 

 

 

 

 

 

 

TSC_ΔT

2

 

TSC_ΔT

-2

 

TSC_ΔT < 2

-2 > TSC_ΔT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Control value

+ 1 step (Open)

 

 

± 0 step

- 1 step (Close)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Initial value

Driving range

 

 

1 step

Control cycle

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

0-12

3 WV move 7.5 degs

4 mins (FC)

 

 

 

 

 

 

 

 

 

 

 

 

For 2-temperature control, DP_SW12-3 Zone2 "Yes" must be selected.

Related FC

FC No.

Setting item

Default

Setting available range

 

 

 

 

 

0C

Mixing Valve operation time

60

30

- 240 secs

 

 

 

 

 

59

Mixing Valve control time

4

1

- 30 mins

 

 

 

 

 

6)Q-H characteristics of hydro unit

The following shows the Q-H characteristics.

6-1) HWS-801XWHM3-E, T6-E

Hydraulic heat exchanger(8kW)QH characteristics

Minimum flow rate

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

 

 

 

 

 

 

head(m)

6

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pump

4

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SW3

 

 

2

 

 

 

 

SW2

 

 

 

 

 

 

 

 

 

 

 

1

 

Out of

 

 

 

 

 

 

 

Operation

 

SW1

 

 

 

 

 

 

 

 

 

 

 

 

 

Range

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

20

25

30

 

10

Flow rate(L/min)

6-2) HWS-1402XWHM3-E, T6-E, T9-E

 

 

Hydraulic heat exchanger(14kW)QH characteristics

 

 

 

 

 

 

 

 

 

 

 

Minimum flow rate

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

head(m)

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pump

4

 

 

 

 

 

 

 

 

 

 

 

 

SW3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Out of Operation

 

 

 

 

 

SW2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

Range

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SW1

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

10

15

 

20

25

30

35

40

45

50

55

60

65

 

0

 

Flow rate(L/min)

53

Page 54
Image 54