9-4-3. Temperature sensor, temperature-resistance characteristic table

TC, TWI, TWO, TFI, TTW, TE, TS, TO sensors

Typical value

Temperature

 

Resistance value (kΩ)

 

 

 

 

 

 

(°C)

(Minimum)

 

(Standard)

 

(Maximum)

 

 

 

 

 

 

 

 

 

-10

55.42

 

55.73

 

60.04

 

 

 

 

 

 

0

32.33

 

33.80

 

35.30

 

 

 

 

 

 

10

19.63

 

20.35

 

21.09

 

 

 

 

 

 

20

12.23

 

12.59

 

12.95

 

 

 

 

 

 

25

9.75

 

10.00

 

10.25

 

 

 

 

 

 

30

7.764

 

7.990

 

8.218

 

 

 

 

 

 

40

5.013

 

5.192

 

5.375

 

 

 

 

 

 

50

3.312

 

3.451

 

3.594

 

 

 

 

 

 

60

2.236

 

2.343

 

2.454

 

 

 

 

 

 

70

1.540

 

1.623

 

1.709

 

 

 

 

 

 

80

1.082

 

1.146

 

1.213

 

 

 

 

 

 

90

0.7740

 

0.8237

 

0.8761

 

 

 

 

 

 

100

0.5634

 

0.6023

 

0.6434

 

 

 

 

 

 

TD, TL sensors

Typical value

Temperature

 

Resistance value (kΩ)

 

 

 

 

 

 

(°C)

(Minimum)

 

(Standard)

 

(Maximum)

 

 

 

 

 

 

 

 

 

0

150.5

 

161.3

 

172.7

 

 

 

 

 

 

10

92.76

 

99.05

 

105.6

 

 

 

 

 

 

20

58.61

 

62.36

 

66.26

 

 

 

 

 

 

25

47.01

 

49.93

 

52.97

 

 

 

 

 

 

30

37.93

 

40.22

 

42.59

 

 

 

 

 

 

40

25.12

 

26.55

 

28.03

 

 

 

 

 

 

50

17.00

 

17.92

 

18.86

 

 

 

 

 

 

60

11.74

 

12.34

 

12.95

 

 

 

 

 

 

70

8.269

 

8.668

 

9.074

 

 

 

 

 

 

80

5.925

 

6.195

 

6.470

 

 

 

 

 

 

90

4.321

 

4.507

 

4.696

 

 

 

 

 

 

100

3.205

 

3.336

 

3.468

 

 

 

 

 

 

TC, TWI, TWO, TFI, TTW, TE, TS, TO sensors

Resistance(kΩ)

Resistance(kΩ)(50°C or lower)

60

 

 

 

 

 

 

 

 

 

 

 

50

 

 

 

 

 

 

 

 

 

 

 

40

 

 

 

 

 

 

 

 

 

 

 

30

 

 

 

 

 

 

 

 

 

 

 

20

 

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

0-10

0

10

20

30

40

50

60

70

80

90

100

 

 

 

 

Temperature(°C)

 

 

 

 

 

 

 

 

 

TD, TL sensors

 

 

 

 

 

200

 

 

 

 

 

 

 

 

 

20

°C)(50or higher)

100

 

 

 

 

 

 

 

 

 

10

150

 

 

 

 

 

 

 

 

 

15

 

 

 

 

 

 

 

 

 

 

 

 

Ω

50

 

 

 

 

 

 

 

 

 

5

Resistance(k

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

0

 

0

10

20

30

40

50

60

70

80

90

100

 

 

 

 

 

Temperature(°C)

 

 

 

 

 

*Since the TH sensor (outdoor unit heat-sink temperature sensor) is built in the outdoor control board, the resistance value cannot be measured.