[A03] Error Temperature rise and error short circuit

Start

TTW sensor characteristic is correct

Yes

(TTW Manual background 85°C is detected)

No

Manual background Replace TTW sensor

Hot water cylinder heater

No

is energized

 

Yes

 

Mg-sw (RY05) for

No

 

 

heater operates

 

Operating noise at normal time

 

Yes

 

 

 

 

 

At normal

No

temperature, tank thermostat

 

 

 

is energized

 

 

 

Yes

 

 

 

Replace Mg-sw

Hot water cylinder

No

thermostat operates

 

 

 

 

Operation temperature 82°C

Manual backgroundYes

Replace water heat exchange control board

Replace hot water cylinder thermostat

76

Page 77
Image 77