Toshiba HWS-1402XWHT6-E, HWS-802XWHT6-E, HWS-802H-E, HWS-802XWHM3-E, HWS-1402H-E AUTO operation

Models: HWS-1402XWHT9-E HWS-1402XWHM3-E HWS-1402XWHT6-E HWS-1501CSHM3-E(-UK) HWS-1402H-E HWS-2101CSHM3-E(-UK) HWS-3001CSHM3-E(-UK) HWS-802XWHM3-E HWS-802H-E HWS-802XWHT6-E

1 168
Download 168 pages 43.83 Kb
Page 47
Image 47
Manual background

Item

Operation flow and applicable data, etc.

 

 

8-2.

11) AUTO operation

Operation

An auto operation sets the water temperature TSC_F depending on the outside temperature TO by following the table

Mode and

below.

Control Method

 

1)How to operate

Pressing the remote controller [ZONE1, 2] button and then the [AUTO] button starts AUTO operation for heating. An operation starts at the set temperature of straight -line approximation for the following: water temperature 40°C with the outside temperature -20°C (FC), 35°C with -10 °C (T1)(FC), 30°C with 0°C (FC), 25°C with 10°C (T3), and 20°C with 20°C (TC).

For 2-temperature control, although Auto-Curve in ZONE2 shows 80% of that of ZONE1 (FC), the water temperature setting does not fall below 20°C.

During an AUTO operation, pressing again the [AUTO] button returns to the usual manual set heating operation.

The remote controller displays "A" as the temperature during an AUTO operation. (When 2-temperature control is enabled, the remote controller displays "A" "A".)

Long-pressing the [AUTO] button during an AUTO operation activates the Auto-Curve FC change mode, enabling the set Auto-Curve water temperature to be changed in the ±5K range. (FC_27)

Even if the temperature setting is changed during an AUTO operation, the operation continues.

An AUTO operation works with a heating operation only, not with a cooling or a hot water supply operation.

 

 

 

Auto-Curve

 

 

 

 

 

ZONE1

 

 

40(A)

 

 

 

 

 

35(B)

 

 

 

 

 

30(C)

 

 

 

 

 

25(D)

 

 

 

 

 

20(E)

Auto-Curve

 

 

 

 

ZONE2

 

 

 

 

 

 

 

 

 

 

-20

-10

0

10

20

 

 

(T1)

 

(T3)

 

Related FC

FC No.

Setting item

Default

Setting available range

 

 

 

 

27

Set temperature shift with heating set to Auto

0

-5 to 5 k

 

 

 

 

29

Outside air temperature T1 temperature

-10°C

-15-0°C

 

 

 

 

2B

Outside air temperature T3 temperature

10°C

0-15°C

 

 

 

 

2C

Set temperature when out side air temperature is -20 °C.

40°C

20-55°C

 

 

 

 

2D

Set temperature when out side air temperature is -10 °C (T1).

35°C

20-55°C

 

 

 

 

2E

Set temperature when out side air temperature is 0 °C.

30°C

20-55°C

 

 

 

 

2F

Set temperature when out side air temperature is 10 °C (T3).

25°C

20-55°C

 

 

 

 

30

Set temperature when out side air temperature is 20 °C.

20°C

20-55°C

 

 

 

 

31

Auto-Curve ratio of

80%

0-100%

 

ZONE2

 

 

 

 

 

 

46

Page 47
Image 47
Toshiba HWS-1402XWHT6-E, HWS-802XWHT6-E, HWS-802H-E, HWS-802XWHM3-E, HWS-3001CSHM3-E(-UK), HWS-2101CSHM3-E(-UK) AUTO operation