2) Heater control

Item

Operation flow and applicable data, etc.

 

 

8-3.

2) Heater control

Hydro Unit

2-1) Hot water supply operation

Control

During a hot water heat pump operation, the unit energizes the hot water cylinder heater (2.75 kW) when all the

 

following conditions are met. Note that when the hot water supply set temperature (TSC_F) is reached, the unit stops

 

energizing the heater.

 

• When 30 minutes has passed after the hot water heat pump operation started.

 

• The water inlet temperature (TWI) reaches 50°C.

 

• The hot water cylinder sensor reaches the HP_OFF temperature (45°C-FC).

 

• The HP_ON temperature (38°C-FC) is reached without the hot water HP status.

 

• HOT WATER BOOST operation is in progress.

TTW

 

 

Abnormality detection

85

Z zone

 

Y zone

Diff : 2K

 

 

Heater off

 

TSC_H

X zone

TSC_H-4

 

Heater on

Hot Water Boost

HP_OFF(45)

 

 

Heater on only with

 

 

Hot Water Boost in operation

 

(Heater on without

HP_ON (38)

 

hot water HP)

 

 

(Hot water HP start)

2-2) Heating operation

1)Heater control at the time of heat pump operation

Object to be controlled: Backup heater

The backup heater control starts when 13 minutes has passed after the heating heat pump operation started and select the ZONE (A-D). The backup heater control increases, decreases, or maintains the number of heaters every 10 minutes (FC) depending on the difference between the heating set temperature (TSC_F) and the heater outlet temperature (THO). When the heating set temperature (TSC_F) is reached, the hydro stops energizing the backup heater.

THO

70

E zone

Abnormality detection

 

 

 

 

Diff : 2K

 

D zone

 

Heater off

TSC_F-2

 

 

 

 

Heater output down every

 

C zone

 

5, 10, 15, or 20 minutes

TSC_F-4

 

 

 

 

Diff : 2K

 

B zone

 

KEEP

TSC_F-6

 

 

 

 

Diff : 2K

 

A zone

 

Heater output up every

 

 

 

 

 

 

10, 20, 30, or 40 minutes

 

 

 

 

 

Status

 

 

Heater ON / OFF

 

 

 

 

 

Heater 1

 

Backup heater 3 kW = ON

 

 

 

 

 

Heater 2

 

Backup heater 9 kW = ON

 

 

 

 

 

 

The single-phase model of 3 kW has the backup heater 1 only.

The three-phase model of 6 kW has heater 1+2 of 6 kW.