Toshiba HWS-1402XWHT9-E, HWS-802XWHT6-E, HWS-802H-E, HWS-802XWHM3-E, HWS-3001CSHM3-E(-UK) Item

Models: HWS-1402XWHT9-E HWS-1402XWHM3-E HWS-1402XWHT6-E HWS-1501CSHM3-E(-UK) HWS-1402H-E HWS-2101CSHM3-E(-UK) HWS-3001CSHM3-E(-UK) HWS-802XWHM3-E HWS-802H-E HWS-802XWHT6-E

1 168
Download 168 pages 43.83 Kb
Page 39
Image 39
Manual background

Item

 

 

 

Operation flow and applicable data, etc.

Operation description

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8-1.

4) Cooling operation

 

 

 

 

 

 

 

1. Purpose

Basic

 

 

 

 

 

 

 

 

 

 

 

 

Cooling

Operation

 

 

ZONE1, 2

 

Cooling temperature: 10°C to 25°C

2. Details

 

 

 

button set to "ON"

 

This section performs

 

 

 

 

 

 

 

 

 

 

 

cooling operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

according to cooling

 

 

 

 

 

 

 

 

 

 

 

 

 

conditions specified for

 

 

 

 

 

 

 

Circulation pump "ON/OFF" control

 

 

 

 

 

 

Hydro unit

 

 

 

 

 

the steps in the left.

 

 

 

 

 

Water 3-way valve control

 

 

 

 

 

 

 

control

 

 

 

 

 

 

3. Operations

 

 

 

 

 

Water 2-way valve control

 

 

 

 

 

 

 

 

 

 

 

 

 

1) Set the [ZONE1, 2]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

remote controller

 

 

 

 

 

 

 

 

 

 

 

 

 

button to “ON”.

 

 

 

Operation instruction

 

 

 

 

 

 

 

 

2) The hydro unit

 

 

 

 

 

 

 

 

 

 

 

controller starts to

 

 

 

signal

transmit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

transmit a cooling

 

 

 

 

 

 

 

 

 

 

 

 

 

operation signal to the

 

 

 

 

 

 

 

Number of compressor revolutions control

 

 

outdoor unit control

 

 

 

 

 

 

 

 

 

unit.

 

 

 

Outdoor unit

 

 

Number of outdoor fan motor revolutions control

 

 

3) The hydro unit

 

 

 

control

 

 

Pulse motor valve control

 

 

 

 

controller performs the

 

 

 

 

 

 

 

4-way valve control

 

 

 

 

operation controls

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

shown in the left while

 

 

 

 

 

 

 

 

 

 

 

 

 

also controlling the

 

 

 

 

 

 

 

 

 

 

 

 

 

circulation pump, water

 

NOTE:

 

 

 

 

 

 

 

 

 

 

2-way valve, and water

 

 

 

 

 

 

 

 

 

 

 

3-way valve.

 

 

No coding mode in default setting. When use the cooling mode, please change the

 

 

4) The outdoor unit

 

 

FC02 to “0”.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

controls the

 

 

 

 

 

 

 

 

 

 

 

 

 

compressor, outdoor

 

Related FC

 

 

 

 

 

 

 

fan motor, pulse motor

 

 

 

 

 

 

 

 

valve, and 4-way valve

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FC No.

 

Setting item

 

Default

Setting available range

 

based on the operation

 

 

 

 

 

 

 

 

 

 

 

 

 

signals transmitted by

 

 

02

Cooling mode availability

 

 

1: No

 

0: Yes

 

 

 

 

 

 

 

the hydro unit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

38

Page 39
Image 39
Toshiba HWS-1402XWHT9-E, HWS-802XWHT6-E, HWS-802H-E, HWS-802XWHM3-E, HWS-3001CSHM3-E(-UK), HWS-2101CSHM3-E(-UK) Item