9-5. Operation check by PC board switch

9-5-1. Operation check mode

This mode allows to check the operations of the water 2-way valve, water 3-way valve, mixing valve, and circulating pump.

Operation check mode

(1)Preparation

Turn all of the remote controls "OFF" for the hot water supply and heating.

Turn off the hydro unit and the outdoor unit.

Remove the front panel of the hydro unit.

(2)Operation check

1)Turn on the hydro unit and the outdoor unit.

2)Set SW06_2 to "ON".

3)Rotate switch SW01 to position "1" and press tactile switch SW07 for 5 sec. or longer.

4)Rotating the rotary SW01 allows to check each operation.

5)Set the DIP SW06 "OFF" to finish.

Rotary

Check contents

Remark

switch

 

 

 

 

 

 

 

1

None

 

 

 

 

 

 

2

2WV_W

Alive for approx. 2 sec, not alive for 3

 

 

sec

 

 

 

 

 

 

 

 

3

3WV_W

 

 

 

 

 

 

4

Mixing valve

Alive for 30 sec in the forward direction

 

 

Alive for 30 sec in the reverse direction

 

 

 

 

 

 

 

 

5

Built-in AC pump

Alive / not alive for 20 sec

 

 

 

 

 

6

Extended AC pump 1

Alive / not alive for 20 sec

 

 

 

 

 

7

(Extended AC pump 2)

Alive / not alive for 20 sec

Reserved

 

 

 

 

8

Water heat exchange backup

Repeat heater 1, heater 2, and OFF

The built-in AC pump operates.

heater

every 20 sec

 

 

 

 

 

 

 

9

Hot water cylinder heater

Alive / not alive for 10 sec

 

 

 

 

 

10

Backup heater

Alive / not alive for 10 sec

The built-in AC pump and external AC pump

 

 

operate.

 

 

 

 

 

 

 

11

Check the alarm output.

Output for 10 sec / no output for 10 sec

 

 

 

 

 

12

Check the boiler output.

Output for 10 sec / no output for 10 sec

 

 

 

 

 

13

Check the defrost output.

Output for 10 sec / no output for 10 sec

 

 

 

 

 

14

Check the operation output.

Output for 10 sec / no output for 10 sec

 

 

 

 

 

15

Built-in AC pump continuous

Continuously alive

Do not operate the AC pump alive

operation

 

continuously without any water in hydro unit.

 

 

 

 

 

 