(2) -2. Abnormality indication

(2) -2. Abnormality indication

The current abnormality and the latest abnormality (including the current one) can be identified by the LED D800 to D804 on the outdoor control board.

1)Setting all the SW803 dip switches to OFF indicates the current abnormality status.

2)Setting SW803 dip switch <1> only to ON indicates the previous abnormality (including the current one).

3)An abnormality lights any of the LEDs from D800 to D804.(Indication 1)

4)Pressing the push-button switch SW800 for approx. 1 second switches indication.(Indication 2)

5)When SW800 is again pressed or 2 minutes has passed, the indication 1 status returns.

Current abnormality

Latest abnormality

Legend)

SW803

SW803

 

 

 

4

 

 

 

4

 

 

 

 

3

 

 

 

3

 

 

 

 

2

 

 

 

2

 

 

 

ON

1

 

 

ON

1

 

 

D800 (Yellow)

D801 (Yellow) D802 (Yellow) D803 (Yellow) D804 (Yellow) D805 (Green)

---- Off

---- Light

---- Blink

Indication 1

Indication 2

(Initial indication)

(SW800 operation)

Abnormality details

Remote controller

Abnormality code

 

Normal

---

Discharge temperature sensor (TD) failure

F04

Heat exchanger temperature sensor (TE) failure

F06

Heat exchanger temperature sensor (TL) failure

F07, F06

Outside air temperature sensor (TO) failure

F08

Suction temperature sensor (TS) failure

F12, F06

Heat sink temperature sensor (TH) failure

F13, L29

Heat exchanger, suction sensor (TE, TS) wrong wiring

F15, F06

EEPROM failure

F31, L29

Compressor break down

H01

Compressor lock

H02

Current detection circuit failure

H03

Faulty compressor case thermostat

H04, P04

Not set up the capacity

L10, L29

Communication failure between MCUs

L29

Other abnormality (e.g. Compressor's loss of synchronism)

No abnormality confirmation

Abnormal discharge temperature

P03

Power failure

P05, H03, P04

Heat sink overheat failure

P07, L29

Gas leakage detection

P15, L29

4-way valve reverse failure

P19, L29

Hi pressure protection operation

P20, P04

Fan drive system failure

P22

Compressor drive

P26

Compressor rotor position failure

P29