Toshiba HWS-802XWHM3-E Outdoor Unit Failure Detection, Diagnosis procedure for each check code

Models: HWS-1402XWHT9-E HWS-1402XWHM3-E HWS-1402XWHT6-E HWS-1501CSHM3-E(-UK) HWS-1402H-E HWS-2101CSHM3-E(-UK) HWS-3001CSHM3-E(-UK) HWS-802XWHM3-E HWS-802H-E HWS-802XWHT6-E

1 168
Download 168 pages 43.83 Kb
Page 92
Image 92
9-4-2. Outdoor Unit Failure Detection

9-4-2. Outdoor Unit Failure Detection

Diagnosis procedure for each check code

One check code may indicate multiple symptoms. In such a case, see the LED indication on the outdoor board to narrow down the check details.

The handy remote controller displays a check code only when the same failure repeatedly occurs while the LED on the outdoor board indicates an error even if it occurs only once. This may cause indication inconsistency between the remote controller and LED.

Outdoor board LED indication method

Dip switch setting

Setting 1 only of SW803 to ON indicates the latest failure. Because the error history is recorded, you can see the detail even after the power is once turned off. (Not including outside air temperature sensor (TO) failure)

After check work is done or when outside air temperature sensor (TO) failure is detected, set all the SW803 switches to OFF.

(An abnormality now is indicated.)

Indication switching

One or more LEDs of D800 through D804 lit yellow indicates that a failure occurred. <Indication 1>

With the status above, pressing the SW800 button for one second causes the yellow LED to blink. <Indication 2>

Pressing again SW800 for one second or longer returns to <Indication 1>.

The combination of <Indication 1> and <Indication 2> can determine what kind of abnormality.

<Latest abnormality>

<Abnormality now>

SW803 1 only is ON

SW803 All OFF (Initial status)

 

 

 

 

 

 

 

 

 

 

4

 

 

 

4

 

 

 

3

 

 

 

3

 

 

 

2

 

 

 

2

 

 

ON

1

 

 

ON

1

 

 

 

 

 

 

 

 

 

 

<Indication 1>

<Indication 2>

 

(Normal) (Abnormality occurs)(Press SW800)

D800

(yellow)

 

 

D801

(yellow)

 

 

D802

(yellow)

 

 

D803

(yellow)

 

 

D804

(yellow)

 

 

D805

(green)

 

 

 

(Example of outlet temperature sensor failure)

 

Off

Light

Blink

Check code

Outdoor LED

 

 

Check and Action procedure

 

 

indication

 

(No specific description indicates outdoor unit parts.)

 

 

 

 

 

 

 

 

 

 

 

 

 

[H01]

<Indication 1> <Indication 2>

[Compressor fails]

 

 

 

 

 

 

 

Power voltage is normal.

 

No

 

 

 

 

 

 

 

Improve power line

 

 

 

 

230ACV ± 23V

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wiring connection is

normal.

 

 

 

 

 

 

No

 

Check and correct wiring

 

 

 

 

Compressor lead (Board side, compressor

 

 

 

 

 

 

 

 

 

connection

 

 

 

 

side reactor lead, power lead)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Abnormally over loaded

 

Yes

 

Deal with or remove causes

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check outdoor control board

 

 

 

 

 

 

 

 

 

If defective, replace it

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

91

Page 92
Image 92
Toshiba HWS-802XWHM3-E, HWS-802XWHT6-E, HWS-802H-E Outdoor Unit Failure Detection, Diagnosis procedure for each check code