No.

Exchange parts

Work procedure

Remarks

name

 

 

 

 

 

 

6 Compressor

3. Vacuuming

 

 

Compressor lead

1)Connect the vacuum pump to the charge port of

 

 

 

the gas piping valve to operate the vacuum pump.

 

 

 

2)Perform vacuuming until the vacuum low pressure

 

 

 

gauge shows 1(mmHg).

 

Note)

Open fully the pulse motor valve before vacuuming. With the valve closed, vacuuming between the outdoor unit liquid valve and the pulse motor valve may fail.

How to make pulse motor valve forcible full open

SW804

SW801

Turn on the electric leakage breaker.

Set the SW804 dip switch 1 and 3 on the outdoor unit control board to ON.

Press SW801 on the outdoor unit control board for 1 second or longer.

After pressing SW801 for 1 second or longer, turn off the electric leakage beaker within 2 minutes.

4.Charge refrigerant

1)Add refrigerant whose amount is defined according to the piping length from the valve charge port. (HWS-802H : 1.8kg)

7 Pulse motor valve coil 1. How to remove

1)Perform the step 1-1 and step 3.

Pulse motor valve coil

2)Remove the coil from the pulse motor valve body

 

while pulling the coil upward to release the spring

 

holding the copper pipe.

 

2. How to attach

1)Fix the spring to the copper pipe.

Spring

Pulse motor

 

valve body

144

Page 145