1-2) High temperature release control

Item

Operation flow and applicable data, etc.

 

 

8-3.

1-2) High temperature release control

Hydro Unit

A heat pump operation is performed as shown in the table below according to the TC sensor detecting temperature.

Control

• For the detected temperature, TC (= TWO + 2 degree) of a heat pump operation is used. The values of T7 through

 

T10 vary depending on TWI. (See the table below)

If the compressor frequency instruction from the hydro unit is less then 10 Hz, the compressor stops.

TC > 62°C causes the compressor to stop abnormally. When the compressor restarts 140 seconds after the stop

and TC > 62°C is not detected for 20 minutes, the abnormal stop counter is cleared. 10 times of compressor abnormal stop stops the operation of heat pump, and confirms the abnormality (Display: A11).

* If the heat pump operation is switched to other operation, the abnormality detection counter is reset to 0.

 

 

 

TC (TWO+2)

 

Forcible stop

 

 

Zone

Control operation

 

 

 

 

 

T11

 

 

 

 

R1

Increase compressor frequency by 1.2 Hz every

 

 

 

 

 

 

 

 

 

 

 

 

 

60 secs.

 

 

(62.0°C)

 

 

O (down)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R2

Increase compressor frequency by 0.6 Hz every

 

 

 

 

 

T10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P (slow down)

 

 

 

60 secs.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T9

 

 

 

 

 

 

 

 

 

 

 

 

 

Q (keep)

 

 

 

O

Decrease compressor frequency to 70% every

 

 

 

 

 

T8

 

 

 

 

 

 

10 secs.

 

 

 

 

 

R1

 

R2 (slow up)

 

 

P

Decrease compressor frequency by 3 Hz every

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10 secs.

 

 

 

 

 

T7

(slow up)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S (normal)

 

 

Q

Keep compressor frequency.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TC=TWO+2deg

 

 

 

 

 

(°C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TWI

T7

T8

T9

 

T10

T11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TWI<30

57.0

59.0

60.0

 

61.0

62.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30

 

 

TWI<35

57.0

59.0

60.0

 

61.0

62.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

35

 

 

TWI<40

56.5

58.5

59.5

 

60.5

62.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40

 

 

TWI<45

56.5

58.5

59.5

 

60.5

62.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

45

 

 

TWI<50

56.0

58.0

59.0

 

60.0

62.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

 

 

TWI

56.0

58.0

59.0

 

60.0

62.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1-3) Low temperature release control

A heat pump operation is performed as shown in the table below according to the TC sensor detecting temperature.

For the detected temperature, TC = TWO of a heat pump operation is used. The values of T7 through T10 varies depending on TWI. (See the table below)

If the compressor frequency instruction from the hydro unit is less then 10 Hz, the compressor stops.

TC < 3°C causes the compressor to stop abnormally. When the compressor restarts when 140 seconds has passed after the stop and TC < 3°C is not detected for 20 minutes, the abnormal stop counter is cleared. 10 times

of compressor abnormal stop stops the operation of heat pump, and confirms the abnormality (Display: A11). * If the heat pump operation is switched to other operation, the abnormality detection counter is reset to 0.

 

 

 

 

TC (TWO)

 

S (normal)

 

 

Zone

Control operation

 

 

 

 

 

T7

R1

 

 

 

R1

Increase compressor frequency by 1.2 Hz every

 

 

 

 

 

 

 

 

 

 

 

 

60 secs.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R2 (slow up)

 

 

 

 

 

 

 

 

 

T8

(slow up)

 

 

 

R2

Increase compressor frequency by 0.6 Hz every

 

 

 

 

 

 

Q (keep)

 

 

 

 

60 secs.

 

 

 

 

 

T9

 

 

 

 

 

 

O

Decrease compressor frequency to 70% every

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P (slow down)

 

 

 

10 secs.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P

Decrease compressor frequency by 3 Hz every

 

 

 

 

 

 

 

 

O (down)

 

 

 

 

 

 

 

 

T11

 

 

 

 

 

 

 

10 secs.

 

 

 

 

 

 

 

 

Forcible stop

 

 

Q

Keep compressor frequency.

TC=TWO

 

 

 

(°C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TWI

 

T7

T8

T9

 

T10

T11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TWI<10

 

10.0

8.0

6.0

 

4.0

3.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

 

TWI<15

 

10.5

8.5

6.5

 

4.5

3.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

 

 

TWI<20

 

11.0

9.0

7.0

 

5.0

3.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

 

 

TWI

 

11.5

9.5

7.5

 

5.5

3.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

49