[F18] Error THO sensor failure

Start

THO sensor

No

connector (CN206) is

 

 

connected

 

Yes

 

Correct THO sensor connection

THO sensor

No

 

Replace THO sensor

characteristic is normal

 

(See characteristic table on page 101)

 

 

 

 

Yes

Replace water heat exchange control board

[F19] Error THO sensor detach failure

Start

THO sensor

No

Attach THO sensor

is attached to pipe

 

 

to pipe

 

 

Yes

 

 

 

 

 

 

THO sensor

No

 

Replace THO sensor

characteristic is normal

 

 

(See characteristic table on page 101)

Yes

 

 

 

 

 

TWO sensor

No

 

Replace TWO sensor

characteristic is normal

 

 

(See characteristic table on page 101)

Yes

 

 

 

 

 

 

 

 

Replace water heat exchange control board

 

 

 

 

 

 